USA
Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Select your location
View all Modicon M241 Micro PLC
Schneider Eletric TM241CE24R Picture

TM241CE24R

Green premium brand logo
Schneider Eletric TM241CE24R Picture
TM241CE24R
Green premium brand logo

controller M241 24 IO relay Ethernet

Show more characteristics
  • Product availability
    Stock - Normally stocked in distribution facility
  • Price*
    479.00 USD
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Modicon M241
    product or component type
    Logic controller
    [Us] rated supply voltage
    100...240 V AC
    discrete input number
    14, discrete input 8 fast input IEC 61131-2 Type 1
    discrete output type
    Relay
    Transistor
    discrete output number
    6 relay
    4 transistor 4 fast output
    discrete output voltage
    5...125 V DC relay output
    5...250 V AC relay output
    24 V DC transistor output
    discrete output current
    2 A relay output Q4...Q9)
    0.1 A fast output (PTO mode) TR0...TR3)
    0.5 A transistor output TR0...TR3)
    Complementary
    discrete I/O number
    24
    maximum number of I/O expansion module
    7 local
    14 remote
    supply voltage limits
    85…264 V
    network frequency
    50/60 Hz
    discrete input logic
    Sink or source
    discrete input voltage
    24 V
    discrete input voltage type
    DC
    voltage state 1 guaranteed
    >= 15 V input
    voltage state 0 guaranteed
    <= 5 V input
    discrete input current
    5 mA input
    input impedance
    4.7 kOhm input
    response time
    50 µs turn-on, I0...I13 input
    configurable filtering time
    1 µs fast input
    discrete output logic
    Positive logic (source)
    output voltage limits
    125 V DC relay output
    30 V DC transistor output
    277 V AC relay output
    maximum output frequency
    1 kHz transistor output
    20 kHz fast output (PWM mode)
    100 kHz fast output (PLS mode)
    accuracy
    +/- 0.1 % 0.02…0.1 kHz fast output
    +/- 1 % 0.1…1 kHz fast output
    protection type
    Short-circuit protection transistor output
    Short-circuit and overload protection with automatic reset transistor output
    Reverse polarity protection transistor output
    Without protection relay output
    reset time
    10 ms automatic reset output
    12 s automatic reset fast output
    memory capacity
    8 MB program
    64 MB system memory RAM
    data backed up
    128 MB built-in flash memory backup of user programs
    data storage equipment
    <= 16 GB SD card optional)
    battery type
    BR2032 lithium non-rechargeable 4 year(s)
    backup time
    2 years 77 °F (25 °C)
    execution time for 1 KInstruction
    0.3 ms event and periodic task
    0.7 ms other instruction
    application structure
    8 external event tasks
    3 cyclic master tasks + 1 freewheeling task
    8 event tasks
    4 cyclic master tasks
    realtime clock
    With
    clock drift
    <= 60 s/month 77 °F (25 °C)
    positioning functions
    PTO 4 100 kHz)
    counting input number
    4 fast input (HSC mode) 200 kHz
    14 standard input 1 kHz
    control signal type
    A/B 100 kHz fast input (HSC mode)
    Pulse/direction 200 kHz fast input (HSC mode)
    Single phase 200 kHz fast input (HSC mode)
    integrated connection type
    Non isolated serial link serial 1 RJ45 RS232/RS485
    Non isolated serial link serial 2 removable screw terminal block RS485
    USB port mini B USB 2.0
    Ethernet RJ45
    supply
    Serial 1)serial link supply 5 V, <200 mA
    transmission rate
    1.2...115.2 kbit/s (115.2 kbit/s by default) 49.21 ft (15 m) RS485
    1.2...115.2 kbit/s (115.2 kbit/s by default) 9.84 ft (3 m) RS232
    480 Mbit/s 9.84 ft (3 m) USB
    10/100 Mbit/s Ethernet
    communication port protocol
    Non isolated serial link Modbus master/slave
    port Ethernet
    10BASE-T/100BASE-TX - 1 copper cable
    ethernet services
    FDR
    DHCP server via TM4 Ethernet switch network module
    DHCP client embedded Ethernet port
    SMS notifications
    Updating firmware
    SNMP client/server
    Programming
    NGVL
    Monitoring
    IEC VAR ACCESS
    FTP client/server
    Downloading
    SQL client
    Modbus TCP client I/O scanner
    Ethernet/IP originator I/O scanner embedded Ethernet port
    Ethernet/IP target, Modbus TCP server and Modbus TCP slave
    Send and receive email from the controller based on TCP/UDP library
    Web server (WebVisu & XWeb system)
    OPC UA server
    DNS client
    local signalling
    PWR 1 LED green)
    RUN 1 LED green)
    Module error (ERR) 1 LED red)
    I/O error (I/O) 1 LED red)
    SD card access (SD) 1 LED green)
    BAT 1 LED red)
    SL1 1 LED green)
    SL2 1 LED green)
    Bus fault on TM4 (TM4) 1 LED red)
    I/O state 1 LED per channel green)
    Ethernet port activity 1 LED green)
    electrical connection
    removable screw terminal block for inputs and outputs pitch 5.08 mm)
    removable screw terminal block for connecting the 24 V DC power supply pitch 5.08 mm)
    maximum cable distance between devices
    Unshielded cable <164.04 ft (50 m) input
    Shielded cable <32.81 ft (10 m) fast input
    Unshielded cable <164.04 ft (50 m) output
    Shielded cable <9.84 ft (3 m) fast output
    insulation
    Between supply and internal logic 500 V AC
    Non-insulated between supply and ground
    marking
    CE
    sensor power supply
    24 V DC 400 mA supplied by the controller
    surge withstand
    2 kV power lines (AC) common mode EN/IEC 61000-4-5
    2 kV relay output common mode EN/IEC 61000-4-5
    1 kV shielded cable common mode EN/IEC 61000-4-5
    1 kV power lines (AC) differential mode EN/IEC 61000-4-5
    1 kV relay output differential mode EN/IEC 61000-4-5
    1 kV input common mode EN/IEC 61000-4-5
    1 kV transistor output common mode EN/IEC 61000-4-5
    web services
    Web server
    maximum number of connections
    8 Modbus server
    8 SoMachine protocol
    10 web server
    4 FTP server
    16 Ethernet/IP target
    8 Modbus client
    number of slave
    64 Modbus TCP
    16 Ethernet/IP
    cycle time
    10 ms 16 Ethernet/IP
    64 ms 64 Modbus TCP
    mounting support
    Top hat type TH35-15 rail IEC 60715
    Top hat type TH35-7.5 rail IEC 60715
    plate or panel with fixing kit
    height
    3.54 in (90 mm)
    depth
    3.74 in (95 mm)
    width
    5.91 in (150 mm)
    net weight
    1.17 lb(US) (0.53 kg)
    Environment
    standards
    ANSI/ISA 12-12-01
    CSA C22.2 No 142
    CSA C22.2 No 213
    EN/IEC 61131-2:2007
    Marine specification (LR, ABS, DNV, GL)
    UL 1604
    UL 508
    product certifications
    RCM
    CSA
    IACS E10
    CULus
    resistance to electrostatic discharge
    8 kV in air EN/IEC 61000-4-2
    4 kV on contact EN/IEC 61000-4-2
    resistance to electromagnetic fields
    9.14 V/m (10 V/m) 80 MHz...1 GHz EN/IEC 61000-4-3
    2.74 V/m (3 V/m) 1.4 GHz...2 GHz EN/IEC 61000-4-3
    0.91 V/m (1 V/m) 2 GHz...3 GHz EN/IEC 61000-4-3
    resistance to fast transients
    2 kV EN/IEC 61000-4-4 power lines)
    2 kV EN/IEC 61000-4-4 relay output)
    1 kV EN/IEC 61000-4-4 Ethernet line)
    1 kV EN/IEC 61000-4-4 serial link)
    1 kV EN/IEC 61000-4-4 input)
    1 kV EN/IEC 61000-4-4 transistor output)
    resistance to conducted disturbances
    10 V 0.15...80 MHz EN/IEC 61000-4-6
    3 V 0.1...80 MHz Marine specification (LR, ABS, DNV, GL)
    10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
    electromagnetic emission
    Conducted emissions 120...69 dBµV/m QP power lines)10…150 kHz EN/IEC 55011
    Conducted emissions 63 dBμV/m QP power lines)1.5…30 MHz EN/IEC 55011
    Conducted emissions 79 dBμV/m QP/66 dBμV/m AV power lines)0.15…0.5 MHz EN/IEC 55011
    Conducted emissions 73 dBμV/m QP/60 dBμV/m AV power lines)0.5…300 MHz EN/IEC 55011
    Radiated emissions 40 dBμV/m QP class A 10 m)30…230 MHz EN/IEC 55011
    Conducted emissions 79...63 dBμV/m QP power lines)150…1500 kHz EN/IEC 55011
    Radiated emissions 47 dBμV/m QP class A 10 m)230…1000 MHz EN/IEC 55011
    immunity to microbreaks
    10 ms
    ambient air temperature for operation
    14…122 °F (-10…50 °C) vertical installation)
    14…131 °F (-10…55 °C) horizontal installation)
    ambient air temperature for storage
    -13…158 °F (-25…70 °C)
    relative humidity
    10…95 %, without condensation in operation)
    10…95 %, without condensation in storage)
    IP degree of protection
    IP20 with protective cover in place
    pollution degree
    2
    operating altitude
    0...6561.68 ft (0...2000 m)
    storage altitude
    0.00…9842.52 ft (0…3000 m)
    vibration resistance
    3.5 mm 5…8.4 Hz symmetrical rail
    3 gn 8.4…150 Hz symmetrical rail
    3.5 mm 5…8.4 Hz panel mounting
    3 gn 8.4…150 Hz panel mounting
    shock resistance
    15 gn 11 ms
    Ordering and shipping details
    Category
    22533 - M2XX PLC & ACCESSORIES
    Discount Schedule
    MSX
    GTIN
    00785901949985
    Package weight(Lbs)
    0.76 kg (1.68 lb(US))
    Returnability
    Yes
    Country of origin
    ID
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    California proposition 65
    WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
    REACh Regulation
    EU RoHS Directive
    Pro-active compliance (Product out of EU RoHS legal scope)
    EU RoHS Declaration
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    Environmental Disclosure
    Circularity Profile
    WEEE
    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    PVC free
    Yes
  • Documents

    Language
    • English
    Catalog
    Date
    Size
    Add to My Documents
    Digest 178 Catalog 27: Automation Products (Version 1.0)
    User guide
    Date
    Size
    Add to My Documents
    EcoStruxure Machine Expert Modbus TCP - User Guide (Version 00)
    EcoStruxure Machine Expert EtherNet/IP - User Guide (Version 00)
    Modicon M241 Logic Controller, Hardware Guide (Version 07)
    Modicon M241 Logic Controller, Programming Guide (Version 07)
    CAD
    Date
    Size
    Add to My Documents
    Compact Hardwired Logic Controller M241 - Wiring Diagram (Version 1.0)
    CAD file (on TraceParts) for TM241CE24R: controller M241 24 IO relay Ethernet (Version 2.0)
    CAD for TM241CE24R: controller M241 24 IO relay Ethernet (Version 1.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 10/21/19
    Size 195.3 KB
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 10/21/19
    Size 195.3 KB
    RoHs China Declaration
    Date
    Size
    Add to My Documents
    Date 10/21/19
    Size 195.3 KB
  • Software and Firmware

    Language
    • English
    Firmware - Released
    Date
    Size
    Add to My Documents
    M241 M251 Firmware (Version 4.0.6.39)
    Date 10/24/18
    Size 612.5 KB
    Date 10/24/18
    Size 5.3 MB
    Date 10/24/18
    Size 16.9 MB
    Date 10/24/18
    Size 8.8 MB
    Date 10/24/18
    Size 5.3 MB
    M241 M251 Firmware (Version 4.0.6.38)
    Date 6/19/18
    Size 16.9 MB
    Date 6/19/18
    Size 8.8 MB
    Date 6/19/18
    Size 5.2 MB
    Date 6/19/18
    Size 5.3 MB
    Date 6/19/18
    Size 568 KB
    Firmware - Updates
    Date
    Size
    Add to My Documents
    Last Release Notes (Version 4.0.6.39)
    Date 10/24/18
    Size 612.5 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Mounting and Clearance

    Clearance



    Mounting Position


    Acceptable Mounting


    NOTE: Expansion modules must be mounted above the logic controller.

    Incorrect Mounting



    Direct Mounting On a Panel Surface
    Mounting Hole Layout



  • Connections and Schema

    Digital Inputs
    Wiring Diagram (Positive Logic)


    (*) :
    Type T fuse
    (1) :
    The COM0, COM1 and COM2 terminals are not connected internally.

    Wiring Diagram (Negative Logic)


    (*) :
    Type T fuse
    (1) :
    The COM0, COM1 and COM2 terminals are not connected internally.


    Fast Transistor Outputs
    Wiring Diagram


    (*) :
    2 A fast-blow fuse


    Relay Outputs
    Wiring Diagram


    (*) :
    Type T fuse
    (1) :
    The terminals COM1 to COM4 are not connected internally.
    (2) :
    To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load


    USB Mini-B Connection



    Ethernet Connection to a PC



Compare products: /