USA

Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

controller M221 24 IO relay Ethernet

Show more characteristics >
  • Product availability
    Stock - Normally stocked in distribution facility
  • Price
    319.00 USD
Add to My Products Remove from My Products

  • Main
    range of product
    Modicon M221
    product or component type
    Logic controller
    [Us] rated supply voltage
    100...240 V AC
    discrete input number
    14 discrete input conforming to IEC 61131-2 Type 1
    analogue input number
    2 at input range: 0...10 V
    discrete output type
    Relay normally open
    discrete output number
    10 relay
    discrete output voltage
    5...125 V DC
    5...250 V AC
    discrete output current
    2 A
    Complementary
    discrete I/O number
    24
    number of I/O expansion module
    <= 7 transistor output
    <= 7 relay output
    supply voltage limits
    85...264 V
    network frequency
    50/60 Hz
    inrush current
    <= 40 A
    power consumption in VA
    <= 58 VAat 100...240 V with max number of I/O expansion module
    <= 35 VAat 100...240 V without I/O expansion module
    power supply output current
    0.52 A at 5 V expansion bus
    0.16 A at 24 V expansion bus
    discrete input logic
    Sink or source (positive/negative)
    discrete input voltage
    24 V
    discrete input voltage type
    DC
    analogue input resolution
    10 bits
    LSB value
    10 mV
    conversion time
    1 ms per channel + 1 controller cycle time analog input
    permitted overload on inputs
    +/- 30 V DC analog input with 5 min maximum
    +/- 13 V DC analog input permanent
    voltage state 1 guaranteed
    >= 15 V input
    voltage state 0 guaranteed
    <= 5 V input
    discrete input current
    7 mA discrete input
    5 mA fast input
    input impedance
    4.9 kOhm fast input
    3.4 kOhm discrete input
    100 kOhm analog input
    response time
    10 ms turn-on operation output
    35 µs turn-off operation input; I2...I5 terminal
    10 ms turn-off operation output
    5 µs turn-on operation fast input; I0, I1, I6, I7 terminal
    35 µs turn-on operation input; other terminals terminal
    5 µs turn-off operation fast input; I0, I1, I6, I7 terminal
    100 µs turn-off operation input; other terminals terminal
    configurable filtering time
    0 ms input
    12 ms input
    3 ms input
    output voltage limits
    125 V DC
    277 V AC
    current per output common
    4 Aat COM 2 termnal
    7 A at COM 0 termnal
    7 A at COM 1 termnal
    absolute accuracy error
    +/- 1 % of full scale analog input
    electrical durability
    Inductive AC-15, (cos phi = 0.35) 240 V/ 120 VA: 100000 cycles
    Resistive DC-12, 24 V/ 48 W: 100000 cycles
    Resistive AC-12, 120 V/ 240 VA: 100000 cycles
    Inductive AC-15, (cos phi = 0.35) 240 V/ 36 VA: 300000 cycles
    Resistive AC-12, 120 V/ 80 VA: 300000 cycles
    Inductive (L/R = 7 ms) DC-13, 24 V/ 24 W: 100000 cycles
    Resistive DC-12, 24 V/ 16 W: 300000 cycles
    Inductive (L/R = 7 ms) DC-13, 24 V/ 7.2 W: 300000 cycles
    Inductive AC-14, (cos phi = 0.7) 240 V/ 240 VA: 100000 cycles
    Inductive AC-15, (cos phi = 0.35) 120 V/ 60 VA: 100000 cycles
    Inductive AC-14, (cos phi = 0.7) 240 V/ 72 VA: 300000 cycles
    Inductive AC-15, (cos phi = 0.35) 120 V/ 18 VA: 300000 cycles
    Resistive AC-12, 240 V/ 480 VA: 100000 cycles
    Inductive AC-14, (cos phi = 0.7) 120 V/ 120 VA: 100000 cycles
    Resistive AC-12, 240 V/ 160 VA: 300000 cycles
    Inductive AC-14, (cos phi = 0.7) 120 V/ 36 VA: 300000 cycles
    switching frequency
    20 switching operations/minute with maximum load
    mechanical durability
    >= 20000000 cycles relay output
    minimum load
    1 mA at 5 V DC relay output
    protection type
    Without protection at 5 A
    reset time
    1 s
    memory capacity
    256 kB user application and data RAM with 10000 instructions
    256 kB internal variables RAM
    data backed up
    256 kB built-in flash memory backup of application and data
    data storage equipment
    2 GB SD card optional
    battery type
    BR2032 lithium non-rechargeable, battery life: 4 yr
    backup time
    1 yearat 77 °F (25 °C) by interruption of power supply
    execution time for 1 KInstruction
    0.3 ms event and periodic task
    execution time per instruction
    0.2 µs Boolean
    exct time for event task
    60 µs response time
    maximum size of object areas
    512 %M memory bits
    8000 %MW memory words
    512 %KW constant words
    255 %TM timers
    255 %C counters
    realtime clock
    With
    clock drift
    <= 30 s/monthat 77 °F (25 °C)
    regulation loop
    Adjustable PID regulator up to 14 simultaneous loops
    counting input number
    4 fast input (HSC mode) (counting frequency: 100 kHz), counting capacity: 32 bits
    counter function
    A/B
    Pulse/direction
    Single phase
    integrated connection type
    USB port with connector mini B USB 2.0
    Ethernet with connector RJ45
    Non isolated serial link "serial 1" with connector RJ45 and interface RS232/RS485
    supply
    Serial serial link supplyat 5 V 200 mA
    transmission rate
    1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m - communication protocol: RS485
    1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 9.84 ft (3 m) - communication protocol: RS232
    480 Mbit/s - communication protocol: USB
    communication port protocol
    USB port: USB protocol - SoMachine-Network
    Non isolated serial link: Modbus protocol master/slave - RTU/ASCII or SoMachine-Network
    : Ethernet protocol
    port Ethernet
    10BASE-T/100BASE-TX 1 port with 328.08 ft (100 m) copper cable
    communication service
    DHCP client
    Ethernet/IP adapter
    Modbus TCP server
    Modbus TCP client
    Modbus TCP slave device
    local signalling
    1 LED green SD card access (SD)
    1 LED red BAT
    1 LED per channel green I/O state
    1 LED green SL
    Ethernet network activity green ACT
    Ethernet network link yellow Link (Link Status)
    1 LED red module error (ERR)
    1 LED green PWR
    1 LED green RUN
    electrical connection
    Mini B USB 2.0 connector for a programming terminal
    Terminal block, 3 terminal(s) for connecting the 24 V DC power supply
    Connector, 4 terminal(s) for analogue inputs
    Removable screw terminal block for inputs
    Removable screw terminal block for outputs
    cable distance between devices
    Shielded cable: 10 m for fast input
    Unshielded cable: 30 m for output
    Unshielded cable: 30 m for digital input
    Unshielded cable: 1 m for analog input
    insulation
    2300 V AC between output and internal logic
    Non-insulated between analogue inputs
    500 V AC between input and internal logic
    Non-insulated between analogue input and internal logic
    1500 V AC between supply and ground
    500 V AC between sensor power supply and ground
    500 V AC between input and ground
    1500 V AC between output and ground
    2300 V AC between supply and internal logic
    500 V AC between sensor power supply and internal logic
    500 V AC between Ethernet terminal and internal logic
    2300 V AC between supply and sensor power supply
    marking
    CE
    sensor power supply
    24 V DCat 250 mA supplied by the controller
    mounting support
    Top hat type TH35-15 rail conforming to IEC 60715
    Top hat type TH35-7.5 rail conforming to IEC 60715
    Plate or panel with fixing kit
    height
    3.54 in (90 mm)
    depth
    2.76 in (70 mm)
    width
    4.33 in (110 mm)
    product weight
    0.87 lb(US) (0.395 kg)
    Environment
    standards
    EN/IEC 60664-1
    EN/IEC 61131-2
    EN/IEC 61010-2-201
    product certifications
    ABS
    CSA
    cULus
    LR
    IACS E10
    RCM
    EAC
    DNV-GL
    environmental characteristic
    Ordinary and hazardous location
    resistance to electrostatic discharge
    4 kV on contact conforming to EN/IEC 61000-4-2
    8 kV in air conforming to EN/IEC 61000-4-2
    resistance to electromagnetic fields
    9.14 V/yd (10 V/m) ( 80 MHz...1 GHz) conforming to EN/IEC 61000-4-3
    2.74 V/yd (3 V/m) ( 1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
    1 V/m ( 2...2.7 GHz) conforming to EN/IEC 61000-4-3
    resistance to magnetic fields
    30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
    resistance to fast transients
    2 kV power lines conforming to EN/IEC 61000-4-4
    2 kV relay output conforming to EN/IEC 61000-4-4
    1 kV Ethernet line conforming to EN/IEC 61000-4-4
    1 kV serial link conforming to EN/IEC 61000-4-4
    1 kV I/O conforming to EN/IEC 61000-4-4
    surge withstand
    2 kV power lines (AC) in common mode conforming to EN/IEC 61000-4-5
    2 kV relay output in common mode conforming to EN/IEC 61000-4-5
    1 kV I/O in common mode conforming to EN/IEC 61000-4-5
    1 kV shielded cable in common mode conforming to EN/IEC 61000-4-5
    0.5 kV power lines (DC) in differential mode conforming to EN/IEC 61000-4-5
    1 kV power lines (AC) in differential mode conforming to EN/IEC 61000-4-5
    1 kV relay output in differential mode conforming to EN/IEC 61000-4-5
    0.5 kV power lines (DC) in common mode conforming to EN/IEC 61000-4-5
    resistance to conducted disturbances
    10 Vrms (0.15...80 MHz) conforming to EN/IEC 61000-4-6
    3 Vrms (0.1...80 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
    10 Vrms (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) conforming to Marine specification (LR, ABS, DNV, GL)
    electromagnetic emission
    Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.15...0.5 MHz: 79 dBμV/m QP/66 dBμV/m AV
    Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.5...300 MHz: 73 dBμV/m QP/60 dBμV/m AV
    Conducted emissions conforming to EN/IEC 55011 power lines, 10...150 kHz: 120...69 dBµV/m QP
    Conducted emissions conforming to EN/IEC 55011 power lines, 1.5...30 MHz: 63 dBμV/m QP
    Radiated emissions conforming to EN/IEC 55011 class A 10 m, 30...230 MHz: 40 dBμV/m QP
    Conducted emissions conforming to EN/IEC 55011 power lines, 150...1500 kHz : 79...63 dBμV/m QP
    Radiated emissions conforming to EN/IEC 55011 class A 10 m, 200...1000 MHz : 47 dBμV/m QP
    immunity to microbreaks
    10 ms
    ambient air temperature for operation
    14...131 °F (-10...55 °C) horizontal installation
    -10...35 °C vertical installation
    ambient air temperature for storage
    -13...158 °F (-25...70 °C)
    relative humidity
    10...95 % without condensation in operation
    10...95 % without condensation in storage
    IP degree of protection
    IP20 with protective cover in place
    pollution degree
    <= 2
    operating altitude
    0...6561.68 ft (0...2000 m)
    storage altitude
    0...9842.52 ft (0...3000 m)
    vibration resistance
    3.5 mm (vibration frequency: 5...8.4 Hz) on symmetrical rail
    1 gn (vibration frequency: 8.4...150 Hz) on symmetrical rail
    3.5 mm (vibration frequency: 5...8.4 Hz) on panel mounting
    1 gn (vibration frequency: 8.4...150 Hz) on panel mounting
    shock resistance
    98 m/s² (test wave duration:11 ms)
    Ordering and shipping details
    Category
    22533 - M2XX PLC & ACCESSORIES
    Discount Schedule
    MSX
    GTIN
    00785901146414
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    1.5
    Returnability
    Y
    Country of origin
    TW
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
  • Documents and Downloads

    Language
    • English
    Catalog
    Date
    Size
    Add to My Documents
    Modicon M221 logic controllers (Version 7.0)
    Digest Catalog 27: Automation Products (Version 1.8)
    User guide
    Date
    Size
    Add to My Documents
    Modicon M221 Logic Controller, Hardware Guide (Version 06)
    Modicon M221 - Logic Controller, Programming Guide (Version 09)
    CAD
    Date
    Size
    Add to My Documents
    Compact Hardwired Logic Controller M221 - Wiring Diagram (Version 1.0)
    CAD files for TM221CE24R: CONTROLLER M221-24IO Relay Ethernet Compact (Version 1.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 3/6/19
    Size 0
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 3/6/19
    Size 0
    System user guide
    Date
    Size
    Add to My Documents
    Compact Hardwired Logic Controller M221, System User Guide (Version 00)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Mounting and Clearance

    Mounting on a Rail



    Direct Mounting on a Panel Surface


    (1)
    Install a mounting strip

    Mounting Hole Layout



    Mounting
    Correct Mounting Position


    Acceptable Mounting Position


    Incorrect Mounting Position



    Clearance



  • Connections and Schema

    Digital Inputs
    Wiring Diagram (Positive Logic)


    (*)
    Type T fuse

    Wiring Diagram (Negative Logic)


    (*)
    Type T fuse

    Connection of the Fast Inputs


    I0, I1, I6, I7


    Relay Outputs
    Negative Logic (Sink)


    (*)
    Type T fuse
    (1)
    The COM0, COM1 and COM2 terminals are not connected internally.
    (2)
    To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load
    B
    Sink wiring (negative logic)

    Positive Logic (Source)


    (*)
    Type T fuse
    (1)
    The COM0, COM1 and COM2 terminals are not connected internally.
    (2)
    To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load
    A
    Source wiring (positive logic)


    Analog Inputs



    The (-) poles are connected internally.

    Pin

    Wire Color

    0 V

    Black

    AN1

    Red

    0 V

    Black

    AN0

    Red


    Ethernet Connection


    Pin N°

    Signal

    1

    TD+

    2

    TD-

    3

    RD+

    4

    -

    5

    -

    6

    RD-

    7

    -

    8

    -



    USB Mini-B Connection



    SL1 Connection


    SL1

    N °

    RS 232

    RS 485

    1

    RxD

    N.C.

    2

    TxD

    N.C.

    3

    RTS

    N.C.

    4

    N.C.

    D1

    5

    N.C.

    D0

    6

    CTS

    N.C.

    7

    N.C*.

    5 Vdc

    8

    Common

    Common

    N.C.: not connected

    * : 5 Vdc delivered by the controller. Do not connect.



  • Performance Curves

    Derating Curves
    Embedded Digital Inputs (No Cartridge)


    X :
    Ambient temperature
    Y :
    Input simultaneous ON ratio

    Embedded Digital Inputs (with Cartridge)


    X :
    Ambient temperature
    Y :
    Input simultaneous ON ratio