USA
Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

three-Phase Asymmetry control relay 380…480Vac, 2 C/O

Show more characteristics >
  • Product availability
    Stock - Normally stocked in distribution facility
  • Price
    137.01 USD
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Zelio Control
    product or component type
    Modular measurement and control relays
    relay type
    Control relay
    Phase
    3 phases
    relay name
    RM22TA
    relay monitored parameters
    Asymmetry
    Phase sequence
    Phase failure detection
    time delay type
    Adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
    switching capacity in VA
    2000 VA
    measurement range
    380...480 V voltage AC
    Complementary
    reset time
    <= 1500 ms at maximum voltage
    maximum switching voltage
    250 V AC
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    8 A AC
    [Us] rated supply voltage
    380...480 V AC
    supply voltage limits
    304...576 V AC
    operating limits
    - 20 % + 20 % Un
    power consumption in VA
    15 VA at 480 V AC 60 Hz
    voltage detection threshold
    < 100 V AC
    supply voltage frequency
    50...60 Hz +/- 10 %
    output contacts
    2 C/O
    setting accuracy of the switching threshold
    +/- 10 % of the full scale
    switching threshold drift
    <= 0.05 % per degree centigrade depending permissible ambient air temperature
    <= 1 % within the supply voltage range
    setting accuracy of time delay
    10 P
    time delay drift
    <= 0.05 % per degree centigrade depending permissible ambient air temperature
    <= 1 % within the supply voltage range
    hysteresis
    2 % fixed of selectable
    run-up delay at power-up
    <= 650 ms
    measuring cycle
    150 ms measurement cycle as true rms value
    threshold adjustment voltage
    2...20 % of Un selected
    voltage range
    380...480 V phase to phase
    adjustment of asymmetry threshold
    5...15 % of Un selected
    repeat accuracy
    +/- 0.5 % input and measurement circuit
    +/- 3 % time delay
    measurement error
    < 0.05 %/°C with temperature variation
    < 1 % over the whole range with voltage variation
    response time
    <= 300 ms
    overvoltage category
    III conforming to UL 508
    III conforming to IEC 60664-1
    insulation resistance
    > 100 MOhm at 500 V DC conforming to IEC 60255-27
    mounting position
    Any position
    connections - terminals
    Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
    Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
    Screw terminals 1 x 0.5...1 x 3.3 mm² - AWG 20...AWG 12, solid cable without cable end
    Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 14, flexible cable with cable end
    tightening torque
    5.31...8.85 lbf.in (0.6...1 N.m) conforming to IEC 60947-1
    housing material
    Self-extinguishing plastic
    status LED
    LED yellow relay ON
    LED green power ON
    mounting support
    35 mm DIN rail conforming to EN/IEC 60715
    electrical durability
    100000 cycles
    mechanical durability
    10000000 cycles
    utilisation category
    AC-1 conforming to IEC 60947-4-1
    DC-1 conforming to IEC 60947-4-1
    AC-15 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    safety reliability data
    B10d = 350000
    MTTFd = 388.1 years
    contacts material
    Cadmium free
    width
    0.89 in (22.5 mm)
    product weight
    0.2 lb(US) (0.09 kg)
    Environment
    immunity to microbreaks
    <= 10 ms
    electromagnetic compatibility
    Conducted and radiated emissions class B conforming to CISPR 22
    Immunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1
    Electrostatic discharge 6 kV level 3 contact discharge conforming to IEC 61000-4-2
    Electrostatic discharge 8 kV level 3 air discharge conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test 10 V/m level 3 conforming to IEC 61000-4-3
    Electrical fast transient/burst immunity test 4 kV level 4 direct conforming to IEC 61000-4-4
    Electrical fast transient/burst immunity test 2 kV level 4 capacitive coupling conforming to IEC 61000-4-4
    Surge immunity test 4 kV level 4 common mode conforming to IEC 61000-4-5
    Surge immunity test 2 kV level 4 differential mode conforming to IEC 61000-4-5
    Conducted and radiated emissions class B group 1 conforming to CISPR 11
    Emission standard for industrial environments conforming to EN/IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
    Immunity for industrial environments conforming to EN/IEC 61000-6-2
    standards
    EN/IEC 60255-1
    product certifications
    CE
    China RoHS
    GL
    RCM
    EAC
    CSA
    CCC
    UL
    ambient air temperature for storage
    -40...158 °F (-40...70 °C)
    ambient air temperature for operation
    -20...50 °C at 60 Hz
    -20...60 °C at 50 Hz AC/DC
    relative humidity
    93...97 % at 25...55 °C conforming to IEC 60068-2-30
    vibration resistance
    0.075 mm (f = 10...58.1 Hz) (not in operation) conforming to IEC 60068-2-6
    1 gn (f = 10...58.1 Hz) (not in operation) conforming to IEC 60068-2-6
    0.035 mm (f = 58.1...150 Hz) (in operation) conforming to IEC 60068-2-6
    0.5 gn (f = 58.1...150 Hz) (in operation) conforming to IEC 60068-2-6
    shock resistance
    15 gn for 11 ms (not in operation) conforming to IEC 60068-2-27
    5 gn for 11 ms (in operation) conforming to IEC 60068-2-27
    IP degree of protection
    IP20 on terminals conforming to IEC 60529
    IP40 on housing conforming to IEC 60529
    IP50 on front panel conforming to IEC 60529
    pollution degree
    3 conforming to IEC 60664-1
    3 conforming to UL 508
    dielectric test voltage
    2.5 kV for 1 min AC 50 Hz conforming to IEC 60255-27
    Ordering and shipping details
    Category
    22380 - RELAYS-MEASUREMENT (RM17-RM35)
    Discount Schedule
    CP2
    GTIN
    00785901694311
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    0.20000000000000001
    Returnability
    Y
    Country of origin
    ID
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    Compliant  - since  0701  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
  • Documents and Downloads

    Language
    • English
    CAD
    Date
    Size
    Add to My Documents
    CAD for RM22TA33: three-Phase Asymmetry control relay 380…480Vac, 2 C/O (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    EAC Certificate RM4 RM17 RM22 RM35 (Version 1.0)
    CSA Certificate RM17, RM22, RM35, RM8487 (Version 1.0)
    UL Listed RM17, RM22, RM35, RM8487 (Version 1.0)
    CCC Certificate RM22 RM35 (Version 1.0)
    Date 5/27/19
    Size 1.7 MB
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 7/10/19
    Size 195.3 KB
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 7/10/19
    Size 195.3 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Mounting and Clearance

    Mounting and Clearance
    Rail Mounting



  • Connections and Schema

    3-Phase Control Relay

    Wiring Diagram


    L1,L2,L3 : Supply to be monitored

    11-14,12 : 1st C/O contact of output relay

    21-24,22 : 2nd C/O contact of output relay


  • Technical Description

    Function Diagram
    Phase Sequence Control, Phase Failure Detection (U measured < 0.7 x nominal supply voltage), and Asymmetry Detection


    Legend

    Tt Time delay after crossing of threshold

    L1, L2, L3 Phases of the supply voltage monitored

    A Asymmetry threshold

    H Hysteresis

    11-12, 11-14 Output relay connections

    Relay status: black color = energized.