USA

Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

Schneider Eletric RE22R2MMW Picture

View all Zelio Time

Zelio Time - RE22R2MMW

Relay Output

Schneider Eletric RE22R2MMW Picture
View all Zelio Time
Zelio Time - RE22R2MMW
Relay Output

Multifunction Timer Relay - 12..240 V AC/DC - 2 C/O

Show more characteristics >
  • Product availability
    Non-Stock - Not normally stocked in distribution facility
  • Price
    73.54 USD
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Relay
    device short name
    RE22
    nominal output current
    8 A
    Complementary
    contacts type and composition
    1 C/O timed contact
    1 C/O timed or instantaneous contact
    time delay type
    A
    Ac
    At
    B
    Bw
    C
    D
    Di
    H
    time delay range
    0.1...1 s
    1...10 h
    1...10 min
    1...10 s
    10...100 h
    6...60 min
    6...60 s
    control type
    Front panel rotary knob
    [Us] rated supply voltage
    12...240 V AC/DC
    voltage range
    0.85...1.1 Us
    supply frequency
    50...60 Hz (+/- 5 %)
    connections - terminals
    Screw terminals : 2 x 1.5 mm² with cable end
    Screw terminals : 2 x 2.5 mm² without cable end
    tightening torque
    5.31...8.85 lbf.in (0.6...1 N.m) conforming to IEC 60947-1
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % conforming to IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
    minimum pulse duration
    100 ms (under load)
    30 ms
    insulation resistance
    100 MOhm at 500 V DC conforming to IEC 60664-1
    reset time
    120 ms (on de-energisation)
    immunity to microbreaks
    > 10 ms
    power consumption in VA
    3 VA at 240 V AC
    power consumption in W
    1.5 W at 240 V DC
    breaking capacity
    2000 VA
    minimum switching current
    10 mA 5 V
    maximum switching current
    8 mA
    maximum switching voltage
    250 V
    electrical durability
    100000 cycles for 8 A at 250 V AC for resistive load
    mechanical durability
    10000000 cycles
    [Uimp] rated impulse withstand voltage
    5 kV conforming to IEC 61812-1
    5 kV 1.2...50 µs conforming to IEC 60664-1
    delay response
    < 100 ms
    safety reliability data
    MTTFd = 251.1 years
    B10d = 230000
    mounting position
    Any position in relation to normal vertical mounting plane
    mounting support
    35 mm DIN rail conforming to EN/IEC 60715
    status LED
    Green LED (flashing) timing in progress
    Green LED (steady) power ON
    Yellow LED relay energised
    width
    0.89 in (22.5 mm)
    product weight
    0.21 lb(US) (0.093 kg)
    Environment
    dielectric strength
    2.5 kV for 1 mA/1 minute at 50 Hz conforming to IEC 61812-1
    standards
    EN 61000-6-1
    EN 61000-6-2
    EN 61000-6-3
    EN 61000-6-4
    IEC 61812-1
    directives
    2004/108/EC - electromagnetic compatibility
    2006/95/EC - low voltage directive
    product certifications
    CCC
    CE
    CSA
    cULus
    GL
    RCM
    EAC
    China RoHS
    ambient air temperature for operation
    -4...140 °F (-20...60 °C)
    ambient air temperature for storage
    -22...140 °F (-30...60 °C)
    IP degree of protection
    IP40 (front face) conforming to IEC 60529
    IP20 (terminal block) conforming to IEC 60529
    IP40 (housing) conforming to IEC 60529
    vibration resistance
    20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
    shock resistance
    15 gn (duration = 11 ms) conforming to IEC 60068-2-27
    relative humidity
    93 %, without condensation conforming to IEC 60068-2-30
    electromagnetic compatibility
    Conducted and radiated emissions, class B conforming to EN 55022
    Electrostatic discharge immunity test (test level: 6 kV, level 3 - contact discharge) conforming to EN/IEC 61000-4-2
    Electrostatic discharge immunity test (test level: 8 kV, level 3 - air discharge) conforming to EN/IEC 61000-4-2
    Fast transients immunity test (test level: 1 kV, level 3 - capacitive connecting clip) conforming to IEC 61000-4-4
    Fast transients immunity test (test level: 2 kV, level 3 - direct contact) conforming to IEC 61000-4-4
    Surge immunity test (test level: 1 kV, level 3 - differential mode) conforming to IEC 61000-4-5
    Surge immunity test (test level: 2 kV, level 3 - common mode) conforming to IEC 61000-4-5
    Radiated radio-frequency electromagnetic field immunity test (test level: 10 V, level 3 - 0.15...80 MHz) conforming to IEC 61000-4-6
    Electromagnetic field immunity test (test level: 10 V/m, level 3 - 80 MHz...1 GHz) conforming to IEC 61000-4-3
    Immunity to microbreaks and voltage drops (test level: 30 % - 500 ms) conforming to IEC 61000-4-11
    Immunity to microbreaks and voltage drops (test level: 100 % - 20 ms) conforming to IEC 61000-4-11
    Ordering and shipping details
    Category
    22376 - RELAYS-MEASUREMENT(RM4)
    Discount Schedule
    CP2
    GTIN
    00785901506379
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    0.20000000000000001
    Returnability
    N
    Country of origin
    ID
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
  • Documents and Downloads

    Language
    • English
    CAD
    Date
    Size
    Add to My Documents
    Industrial timing relay multifunction
    Certificate
    Date
    Size
    Add to My Documents
    Date 8/6/18
    Size 1.5 MB
    UL Listed RE17, RE22, REXL, RE48A, RE88857, RE88865, RE88867, RENF22R2MMW
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Connections and Schema

    Internal Wiring Diagram



    Wiring Diagram



  • Technical Description

    Function A : Power on Delay Relay
    Description

    The timing period T begins on energization. After timing, the output(s) relay close(s).


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function Ac : On- and Off-Delay Relay with Control Signal
    Description

    After power-up, closing of the control contact Y1 causes the timing period T to start (timing can be interrupted by operating the Gate control contact G). At the end of this timing period, the relay closes.

    When control contact Y1 re-opens, the timing T starts.At the end of this timing period T

    At the end of this timing period T, the output reverts to its initial position (timing can be interrupted by operating the Gate control contact G).


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function At : Power on Delay Relay (Summation) with Control Signal
    Description

    After power-up, the first opening of control contact Y1 starts the timing. Timing can be interrupted each time control contact closes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output relay closes.


    T = t1+t2+t3


    Function B : Interval Relay with Control Signal
    Description

    After power-up, pulsing or maintaining control contact Y1 starts the timing T. The output relay closes for the duration of the timing period T then reverts to its initial state.



    Function Bw : Double Interval Relay with Control Signal
    Description

    On closing and opening of control contact Y1, the output relay closes for the duration of the timing period T.



    Function C : Off-Delay Relay with Control Signal
    Description

    After power-up and closing of the control contact Y1, the output relay closes. When control contact Y1 re-opens, timing T starts. At the end of the timing period, the output(s) relay revert(s) to its/their initial state.


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function D : Symmetrical Flasher Relay (Starting Pulse Off)
    Description

    Repetitive cycle with two timing periods T of equal duration, with output(s) relay changing state at the end of each timing period T.


    Before power-up Y1 should be permanently connected to A1.

    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function D : Symmetrical Flasher Relay (Starting Pulse On)
    Description

    Repetitive cycle with two timing periods T of equal duration, with output(s) relay changing state at the end of each timing period T.


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function H : Interval Relay
    Description

    On energization of the relay, timing period T starts and the output(s) relay close(s). At the end of the timing period T, the output(s) relay revert(s) to its/their initial state


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    Y1 :

    Control contact

    R1/R2 :

    2 timed outputs

    R2 inst. :

    The second output is instantaneous if the right position is selected

    T :

    Timing period

    U :

    Supply