USA
Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Select your location
View all Zelio Time
Schneider Eletric RE22R1CMR Picture

RE22R1CMR

Schneider Eletric RE22R1CMR Picture
RE22R1CMR

Off-delay Timing Relay - 0.05s…300h - 24…240V AC/DC - 1C/O

Show more characteristics >
  • Product availability
    Stock - Normally stocked in distribution facility
  • Price*
    59.65 USD
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Relay
    device short name
    RE22
    nominal output current
    8 A
    Complementary
    contacts type and composition
    1 C/O timed contact, cadmium free
    time delay type
    C
    Ct
    time delay range
    10...100 s
    3...30 s
    0.05...1 s
    30...300 s
    30...300 h
    30...300 min
    3...30 min
    3...30 h
    0.3...3 s
    1...10 s
    control type
    Rotary knob
    Diagnostic button
    Potentiometer external
    [Us] rated supply voltage
    24...240 V AC/DC 50/60 Hz
    Release input voltage
    <= 2.4 V
    voltage range
    0.85...1.1 Us
    supply frequency
    50...60 Hz +/- 5 %
    connections - terminals
    Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end
    Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
    Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
    Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
    tightening torque
    5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale 25 °C IEC 61812-1
    Control signal pulse width
    100 ms with load in parallel
    30 ms
    insulation resistance
    100 MOhm 500 V DC IEC 60664-1
    Recovery time
    120 ms on de-energisation
    immunity to microbreaks
    10 ms
    power consumption in VA
    3 VA 240 V AC
    power consumption in W
    1.5 W 240 V DC
    switching capacity in VA
    2000 VA
    minimum switching current
    10 mA 5 V DC
    maximum switching current
    8 A
    maximum switching voltage
    250 V AC
    electrical durability
    100000 cycles, 8 A 250 V, AC-1
    100000 cycles, 2 A 24 V, DC-1
    mechanical durability
    10000000 cycles
    Rated impulse withstand voltage
    5 kV 1.2…50 µs IEC 60664-1
    Power on delay
    100 ms
    creepage distance
    4 kV/3 IEC 60664-1
    overvoltage category
    III IEC 60664-1
    safety reliability data
    MTTFd = 205.4 years
    B10d = 190000
    mounting position
    Any position
    mounting support
    35 mm DIN rail EN/IEC 60715
    status LED
    Green LED backlight steady)dial pointer indication
    Yellow LED steady)output relay energised
    Yellow LED fast flashing)timing in progress and output relay de-energised
    Yellow LED slow flashing)timing in progress and output relay energised
    width
    0.89 in (22.5 mm)
    net weight
    0.22 lb(US) (0.1 kg)
    Environment
    dielectric strength
    2.5 kV 1 mA/1 minute 50 Hz between relay output and power supply basic insulation IEC 61812-1
    standards
    UL 508
    IEC 61812-1
    directives
    2004/108/EC - electromagnetic compatibility
    2006/95/EC - low voltage directive
    product certifications
    UL
    CE
    CCC
    CSA
    China RoHS
    GL
    RCM
    EAC
    ambient air temperature for operation
    -4…140 °F (-20…60 °C)
    ambient air temperature for storage
    -40…158 °F (-40…70 °C)
    IP degree of protection
    Housing IP40 IEC 60529
    Front face IP50 IEC 60529
    Terminals IP20 IEC 60529
    pollution degree
    3 IEC 60664-1
    vibration resistance
    20 m/s² 10…150 Hz)IEC 60068-2-6
    shock resistance
    15 gn not operating 11 ms IEC 60068-2-27
    5 gn in operation 11 ms IEC 60068-2-27
    relative humidity
    95 % 77…131 °F (25…55 °C)
    electromagnetic compatibility
    Fast transients immunity test 1 kV capacitive connecting clip)level 3 IEC 61000-4-4
    Surge immunity test 1 kV differential mode)level 3 IEC 61000-4-5
    Surge immunity test 2 kV common mode)level 3 IEC 61000-4-5
    Electrostatic discharge 6 kV contact discharge)level 3 IEC 61000-4-2
    Electrostatic discharge 8 kV air discharge)level 3 IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test 10 V/m 80 MHz...1 GHz)level 3 IEC 61000-4-3
    Conducted RF disturbances 10 V 0.15...80 MHz)level 3 IEC 61000-4-6
    Fast transient bursts 2 kV direct contact)level 3 IEC 61000-4-4
    Immunity to microbreaks and voltage drops 30 % 500 ms) IEC 61000-4-11
    Immunity to microbreaks and voltage drops 100 % 20 ms) IEC 61000-4-11
    Ordering and shipping details
    Category
    22376 - RELAYS-MEASUREMENT(RM4)
    Discount Schedule
    CP2
    GTIN
    00785901453703
    Package weight(Lbs)
    0.10 kg (0.22 lb(US))
    Returnability
    Yes
    Country of origin
    ID
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    REACh Regulation
    EU RoHS Directive
    Pro-active compliance (Product out of EU RoHS legal scope)
    EU RoHS Declaration
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    Environmental Disclosure
    Circularity Profile
  • Documents and Downloads

    Language
    • English
    CAD
    Date
    Size
    Add to My Documents
    CAD for RE22R1CMR: Off-delay Timing Relay - 0.05s…300h - 24…240V AC/DC - 1C/O (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    UL Listed RE17, RE22, REXL, RE48A, RE88857, RE88865, RE88867, RENF22R2MMW (Version 1.0)
    Zelio Timer RE22 and RENF22R2MMW (Version 1.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 9/19/19
    Size 195.3 KB
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 9/19/19
    Size 195.3 KB
    RoHs China Declaration
    Date
    Size
    Add to My Documents
    Date 9/19/19
    Size 195.3 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Connections and Schema

    Wiring Diagram



  • Technical Description

    Function C: Off-Delay Relay with Control Signal
    Description

    After energisation of power supply and energization of Y1 causes output(s) R close(s). When Y1 deenergizes, timing T starts.At the end of this timing period T,the output(s) R revert(s) to its/their initial position.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").

    Function: 1 Output


    Function: 2 Outputs



    Function Ct: Off-Delay Relay with Control Signal & With Pause / Summation Control
    Description

    After energisation of power supply and energization of Y1 cause output(s) R close(s).When Y1 deenergizes, timing starts and the timing can be interrupted / paused each time X1 energizes. When the cumulative total of time periods elapsedreaches the pre-set value T, the output(s) R revert(s) to its/their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").

    Function: 1 Output


    T =
    t1 + t2 +…

    Function: 2 Outputs


    T =
    t1 + t2 +…

    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    U -

    Supply

    T -

    Timing period

    R1/R2 -

    2 timed outputs

    R2 inst. -

    The second output is instantaneous if the right position is selected

    X1 -

    Pause / Summation control

    Y1 -

    Retrigger / Restart control


Compare products: /