USA
Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Select your location
View all Zelio Time
Schneider Eletric RE17LHBM Picture

RE17LHBM

Schneider Eletric RE17LHBM Picture
RE17LHBM

on-delay timing relay - 1 s..100 h - 24..240 V AC/DC - solid state output

Show more characteristics >
  • Product availability
    Non-Stock - Not normally stocked in distribution facility
  • Price*
    42.90 USD
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Solid state
    width
    0.69 in (17.5 mm)
    component name
    RE17L
    time delay type
    H
    time delay range
    1...10 s
    1...10 h
    0.1...1 s
    6...60 s
    6...60 min
    1...10 min
    10...100 h
    nominal output current
    0.7 A
    Complementary
    control type
    Selector switch front panel
    [Us] rated supply voltage
    24...240 V AC 50/60 Hz
    voltage range
    0.85...1.1 Us
    supply frequency
    50...60 Hz +/- 5 %
    release of input voltage
    9 V
    control signal pulse width
    0.05 s typical
    insulation resistance
    100 MOhm 500 V DC IEC 60664-1
    [Uimp] rated impulse withstand voltage
    5 kV 1.2/50 µs
    power on delay
    100 ms
    connections - terminals
    Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end
    Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
    Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
    Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
    tightening torque
    5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
    dielectric strength
    2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale 25 °C IEC 61812-1
    reset time
    350 ms on de-energisation typical
    on-load factor
    100 %
    power consumption in VA
    0…3 VA 240 V AC
    maximum power consumption in W
    1.5 W 240 V DC
    breaking capacity
    0.5 A AC/DC UL
    0.7 A AC/DC 68 °F (20 °C)
    operating frequency
    10 Hz
    maximum output current
    20 A <= 10 ms
    minimum switching current
    10 mA
    maximum leakage current
    5 mA
    maximum switching voltage
    250 V AC
    maximum voltage drop
    <4 V 3-wire
    <8 V 2-wire
    electrical durability
    100000000 cycles
    marking
    CE
    creepage distance
    4 kV/3 IEC 60664-1
    safety reliability data
    MTTFd = 353.8 years
    B10d = 320000
    mounting position
    Any position in relation to normal vertical mounting plane
    mounting support
    35 mm DIN rail EN/IEC 60715
    net weight
    0.15 lb(US) (0.068 kg)
    time delay type
    H
    functionality
    On-delay timing
    compatibility code
    RE17
    Environment
    immunity to microbreaks
    20 ms
    derating factor
    5 mA/°C
    standards
    2006/95/EC
    EN 61000-6-1
    EN 61000-6-3
    EN 61000-6-2
    IEC 61812-1
    EN 61000-6-4
    2004/108/EC
    product certifications
    CULus
    CSA
    GL
    ambient air temperature for storage
    -22…140 °F (-30…60 °C)
    ambient air temperature for operation
    -4…140 °F (-20…60 °C)
    IP degree of protection
    IP20 IEC 60529 terminal block)
    IP40 IEC 60529 housing)
    IP50 IEC 60529 front panel)
    vibration resistance
    20 m/s² 10…150 Hz)IEC 60068-2-6
    shock resistance
    15 gn 11 ms IEC 60068-2-27
    relative humidity
    93 % without condensation IEC 60068-2-30
    electromagnetic compatibility
    Electrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2
    Electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2
    Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3
    Electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4
    Electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4
    1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5
    1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5
    Conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6
    Voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11
    Voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11
    Conducted and radiated emissionsclass B EN 55022
    Ordering and shipping details
    Category
    22370 - RE, RM MISC TIMERS & COUNTERS
    Discount Schedule
    CP2
    GTIN
    00785901002901
    Package weight(Lbs)
    0.57 kg (1.25 lb(US))
    Returnability
    No
    Country of origin
    ID
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    REACh Regulation
    EU RoHS Directive
    Pro-active compliance (Product out of EU RoHS legal scope)
    EU RoHS Declaration
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    Environmental Disclosure
    Circularity Profile
  • Documents and Downloads

    Language
    • English
    Catalog
    Date
    Size
    Add to My Documents
    Digest 178 Catalog 23: Relays and Timers (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    UL Listed RE17, RE22, REXL, RE48A, RE88857, RE88865, RE88867, RENF22R2MMW (Version 1.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    REACh Declaration
    Date
    Size
    Add to My Documents
    RoHs China Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Width 17.5 mm



  • Connections and Schema

    Internal Wiring Diagram



    Wiring Diagram



  • Technical Description

    Function H : Interval Relay
    Description

    On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    C

    Control contact

    G

    Gate

    R

    Relay or solid state output

    R1/R2

    2 timed outputs

    R2 inst.

    The second output is instantaneous if the right position is selected

    T

    Timing period

    Ta -

    Adjustable On-delay

    Tr -

    Adjustable Off-delay

    U

    Supply


Compare products: /