off-delay timing relay - control - 1 s..100 h - 24..240 V - solid state output

Show more characteristics >
  • Product availability
    Stock - Normally stocked in distribution facility
  • Price
    52.00 USD
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Solid state
    width
    0.69 in (17.5 mm)
    component name
    RE17L
    time delay type
    C
    time delay range
    0.1...1 s
    1...10 h
    1...10 min
    1...10 s
    10...100 h
    6...60 min
    6...60 s
    nominal output current
    0.7 A
    Complementary
    control type
    Selector switch on front panel
    [Us] rated supply voltage
    24...240 V AC at 50/60 Hz
    voltage range
    0.85...1.1 Us
    supply frequency
    50...60 Hz (+/- 5 %)
    release of input voltage
    7 V
    control signal pulse width
    0.05 s typical
    insulation resistance
    100 MOhm at 500 V DC conforming to IEC 60664-1
    [Uimp] rated impulse withstand voltage
    5 kV (1.2/50 µs)
    power on delay
    < 100 ms
    connections - terminals
    Screw terminals, clamping capacity: 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12 (solid) without cable end
    Screw terminals, clamping capacity: 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14 (solid) without cable end
    Screw terminals, clamping capacity: 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14 (flexible) with cable end
    Screw terminals, clamping capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16 (flexible) with cable end
    tightening torque
    5.31...8.85 lbf.in (0.6...1 N.m) conforming to IEC 60947-1
    dielectric strength
    2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % conforming to IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
    reset time
    350 ms on de-energisation typical
    on-load factor
    100 %
    power consumption in VA
    0...3 VA at 240 V AC
    power consumption in W
    <= 1.5 W at 240 V DC
    breaking capacity
    0.5 A AC/DC conforming to UL
    0.7 A AC/DC at 68 °F (20 °C)
    operating frequency
    10 Hz
    maximum output current
    20 A <= 10 ms
    minimum switching current
    10 mA
    leakage current
    < 5 mA
    maximum switching voltage
    250 V AC
    voltage drop
    4 V 3-wire
    8 V 2-wire
    electrical durability
    100000000 cycles
    marking
    CE
    creepage distance
    4 kV/3 conforming to IEC 60664-1
    safety reliability data
    MTTFd = 353.8 years
    B10d = 320000
    mounting position
    Any position in relation to normal vertical mounting plane
    mounting support
    35 mm DIN rail conforming to EN/IEC 60715
    product weight
    0.15 lb(US) (0.068 kg)
    Environment
    immunity to microbreaks
    <= 20 ms
    derating factor
    5 mA/°C
    standards
    2004/108/EC
    EN 61000-6-1
    EN 61000-6-2
    EN 61000-6-3
    EN 61000-6-4
    IEC 61812-1
    2006/95/EC
    product certifications
    CSA
    cULus
    GL
    ambient air temperature for storage
    -22...140 °F (-30...60 °C)
    ambient air temperature for operation
    -4...140 °F (-20...60 °C)
    IP degree of protection
    IP20 (terminal block) conforming to IEC 60529
    IP40 (housing) conforming to IEC 60529
    IP50 (front panel) conforming to IEC 60529
    vibration resistance
    20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
    shock resistance
    15 gn (duration = 11 ms) conforming to IEC 60068-2-27
    relative humidity
    93 % without condensation conforming to IEC 60068-2-30
    electromagnetic compatibility
    Electrostatic discharge immunity test, in contact at 6 kV conforming to IEC 61000-4-2 level 3
    Electrostatic discharge immunity test, in air at 8 kV conforming to IEC 61000-4-2 level 3
    Susceptibility to electromagnetic fields, 80 MHz to 1 GHz at 10 V/m conforming to IEC 61000-4-3 level 3
    Electrical fast transient/burst immunity test, capacitive connecting clip at 1 kV conforming to IEC 61000-4-4 level 3
    Electrical fast transient/burst immunity test, direct at 2 kV conforming to IEC 61000-4-4 level 3
    1.2/50 µs shock waves immunity test, differential mode at 1 kV conforming to IEC 61000-4-5 level 3
    1.2/50 µs shock waves immunity test, common mode at 2 kV conforming to IEC 61000-4-5 level 3
    Conducted RF disturbances, 0.15...80 MHz at 10 V conforming to IEC 61000-4-6 level 3
    Voltage dips and interruptions immunity test, 1 cycle at 0 % conforming to IEC 61000-4-11
    Voltage dips and interruptions immunity test, 25/30 cycles at 70 % conforming to IEC 61000-4-11
    Conducted and radiated emissions conforming to EN 55022 class B
    Ordering and shipping details
    Category
    22370 - RE, RM MISC TIMERS & COUNTERS
    Discount Schedule
    CP2
    GTIN
    00785901147244
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    0.14999999999999999
    Returnability
    Y
    Country of origin
    ID
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
  • Documents and Downloads

    Language
    • English
    Catalog
    Date
    Size
    Add to My Documents
    Digest 178 Catalog 23: Relays and Timers (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    UL Listed RE17, RE22, REXL, RE48A, RE88857, RE88865, RE88867, RENF22R2MMW (Version 1.0)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Width 17.5 mm



  • Connections and Schema

    Internal Wiring Diagram



    Wiring Diagram



  • Technical Description

    Function C : Off-Delay Relay with Control Signal
    Description

    After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    C

    Control contact

    G

    Gate

    R

    Relay or solid state output

    R1/R2

    2 timed outputs

    R2 inst.

    The second output is instantaneous if the right position is selected

    T

    Timing period

    Ta -

    Adjustable On-delay

    Tr -

    Adjustable Off-delay

    U

    Supply