  • Main
    range of product
    PowerLogic PM700
    device short name
    PM700
    product or component type
    Power meter
    Complementary
    power quality analysis
    Total harmonic distortion
    type of measurement
    Energy
    Power factor (total)
    Apparent power (total)
    Apparent power (per phase)
    Active power (total)
    Active power (per phase)
    Reactive power (total)
    Reactive power (per phase)
    Voltage
    Current
    Frequency
    supply voltage
    125...250 V DC
    115...415 V AC (45...65 Hz)
    network frequency
    45...65 Hz
    power consumption in VA
    5 VA
    display type
    Backlit LCD
    display resolution
    6 lines
    sampling rate
    32 samples/cycle
    measurement current
    5 A
    1 A
    input type
    Current 0.005...6 A (impedance <= 0.1 Ohm)
    measurement voltage
    10...480 V AC 45...65 Hz phase to phase
    10...277 V AC 45...65 Hz phase to neutral
    measurement accuracy
    ± 1 % power
    ± 0.5 % current (1...6 A)
    ± 0.5 % voltage (50...227 V)
    ± 0.02 Hz frequency (45...65 Hz)
    ± 0.0034 power factor (1A to 6A and from -0.5 to +0.5)
    accuracy class
    Class 2 (reactive energy according to IEC 62053-23)
    Class 1 (active energy according to IEC 62053-21)
    number of outputs
    2 pulse
    data recording
    Min/max of instantaneous values
    Environment
    electromagnetic compatibility
    Limits for harmonic current emissions, conforming to IEC 61000-3-2
    Conducted and radiated emissions, conforming to EN 55011 class B
    Susceptibility to electromagnetic fields class class III, conforming to IEC 61000-4-3
    Conducted RF disturbances class class III, conforming to IEC 61000-4-6
    Electrostatic discharge immunity test class class III, conforming to IEC 61000-4-2
    Electrical fast transient/burst immunity test class class III, conforming to IEC 61000-4-4
    1.2/50 µs shock waves immunity test class class III, conforming to IEC 61000-4-5
    Immunity to impulse waves class class III, conforming to IEC 61000-4-8
    Immunity to microbreaks and voltage drops class class III, conforming to IEC 61000-4-11
    Limitation of voltage changes, voltage fluctuations and flicker in low-voltage, conforming to IEC 61000-3-3
    mounting mode
    Flush-mounted
    mounting support
    Panel
    type of installation
    Indoor installation
    overvoltage category
    III
    IP degree of protection
    IP30 (back) conforming to IEC 60529
    IP52 (front face) conforming to IEC 60529
    relative humidity
    95 % 122 °F (50 °C)
    pollution degree
    2
    ambient air temperature for operation
    23...140 °F (-5...60 °C) (meter)
    14...131 °F (-10...55 °C) (display)
    ambient air temperature for storage
    -40...185 °F (-40...85 °C)
    operating altitude
    0...9842.52 ft (0...3000 m)
    standards
    IEC 61010-1
    UL 508
    CSA C22.2 No 14
    product certifications
    CE
    cULus
    width
    3.78 in (96 mm)
    depth
    2.72 in (69 mm)
    height
    3.78 in (96 mm)
    product weight
    0.82 lb(US) (0.37 kg)
    Ordering and shipping details
    Category
    09786 - SE ENTRY POWER METER
    Discount Schedule
    PL1
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    1.5
    Returnability
    Y
    Country of origin
    MX
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    Compliant  - since  0951  -  Schneider Electric declaration of conformity
    Schneider Electric declaration of conformity
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    CAD
    Date
    Size
    Add to My Documents
    POWER METER (Version 1.0)
    Date 8/12/13
    Size 382.6 KB
    Date 8/12/13
    Size 436 KB
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.