USA

Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

Schneider Eletric LC1K0910B7TQ Picture

View all TeSys K Miniature Contactors

TeSys K Miniature Contactors - LC1K0910B7TQ

Legacy Products

Schneider Eletric LC1K0910B7TQ Picture
View all TeSys K Miniature Contactors
TeSys K Miniature Contactors - LC1K0910B7TQ
Legacy Products

contactor TeSys LC1-K - 3 poles - AC-3 440V 9 A - coil 24 V AC

Show more characteristics >
  • Product availability
    Non-Stock - Not normally stocked in distribution facility
  • Price
    75.00 USD
Add to My Products Remove from My Products

  • Main
    range of product
    TeSys K
    range
    TeSys
    product or component type
    Contactor
    device short name
    LC1K
    contactor application
    Motor control
    Resistive load
    utilisation category
    AC-1
    AC-3
    AC-4
    control circuit type
    AC
    coil type
    AC 50/60 Hz
    poles description
    3P
    pole contact composition
    3 NO
    [Ie] rated operational current
    20 A (<= 122 °F (50 °C)) AC AC-1 power circuit
    9 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit
    motor power kW
    2.2 kW at 400 V AC 50/60 Hz AC-4
    2.2 kW at 220...230 V AC 50/60 Hz AC-3
    4 kW at 440/500 V AC 50/60 Hz AC-3
    4 kW at 660/690 V AC 50/60 Hz AC-3
    4 kW at 380...415 V AC 50/60 Hz AC-3
    motor power hp
    2 hp at 200/208 V AC 60 Hz conforming to CSA
    2 hp at 200/208 V AC 60 Hz conforming to UL
    3 hp at 230/240 V AC 60 Hz conforming to CSA
    3 hp at 230/240 V AC 60 Hz conforming to UL
    5 hp at 460/480 V AC 60 Hz conforming to CSA
    5 hp at 460/480 V AC 60 Hz conforming to UL
    5 hp at 575/600 V AC 60 Hz conforming to CSA
    5 hp at 575/600 V AC 60 Hz conforming to UL
    auxiliary contact composition
    1 NO
    [Uc] control circuit voltage
    24 V AC 50/60 Hz
    connections - terminals
    Power circuit: screw clamp terminal 1 cable 0 in² (1.5 mm²) - cable stiffness: solid
    Power circuit: screw clamp terminal 2 cable 0.01 in² (4 mm²) - cable stiffness: solid
    Power circuit: screw clamp terminal 1 cable 0 in² (0.75 mm²) - cable stiffness: flexible
    Power circuit: screw clamp terminal 2 cable 0.01 in² (4 mm²) - cable stiffness: flexible
    Power circuit: screw clamp terminal 1 cable 0 in² (0.34 mm²) - cable stiffness: flexible
    Power circuit: screw clamp terminal 1 cable 0 in² (1.5 mm²) - cable stiffness: flexible
    Power circuit: screw clamp terminal 1 cable 0 in² (2.5 mm²) - cable stiffness: flexible
    Control circuit: screw clamp terminal 1 cable 0 in² (1.5 mm²) - cable stiffness: solid
    Control circuit: screw clamp terminal 2 cable 0.01 in² (4 mm²) - cable stiffness: solid
    Control circuit: screw clamp terminal 1 cable 0 in² (0.75 mm²) - cable stiffness: flexible
    Control circuit: screw clamp terminal 2 cable 0.01 in² (4 mm²) - cable stiffness: flexible
    Control circuit: screw clamp terminal 1 cable 0 in² (0.34 mm²) - cable stiffness: flexible
    Control circuit: screw clamp terminal 1 cable 0 in² (1.5 mm²) - cable stiffness: flexible
    Control circuit: screw clamp terminal 1 cable 0 in² (2.5 mm²) - cable stiffness: flexible
    Power circuit: spring terminal 1 cable 0 in² (0.75 mm²) - cable stiffness: solid
    Power circuit: spring terminal 1 cable 0 in² (1.5 mm²) - cable stiffness: solid
    Power circuit: spring terminal 1 cable 0 in² (0.75 mm²) - cable stiffness: flexible
    Power circuit: spring terminal 1 cable 0 in² (1.5 mm²) - cable stiffness: flexible
    Control circuit: spring terminal 1 cable 0 in² (0.75 mm²) - cable stiffness: solid
    Control circuit: spring terminal 1 cable 0 in² (1.5 mm²) - cable stiffness: solid
    Control circuit: spring terminal 1 cable 0 in² (0.75 mm²) - cable stiffness: flexible
    Control circuit: spring terminal 1 cable 0 in² (1.5 mm²) - cable stiffness: flexible
    Power circuit: Faston connectors 2 - width: 0.11 in (2.8 mm) - cable stiffness: clip
    Power circuit: Faston connectors 1 - width: 0.25 in (6.35 mm) - cable stiffness: clip
    Control circuit: Faston connectors 2 - width: 0.11 in (2.8 mm) - cable stiffness: clip
    Control circuit: Faston connectors 1 - width: 0.25 in (6.35 mm) - cable stiffness: clip
    Complementary
    coil technology
    Without built-in bidirectional peak limiting diode suppressor
    control circuit voltage limits
    >= 0.20 Uc at <= 122 °F (50 °C) drop-out 50/60 Hz
    0.8...1.15 Uc at <= 122 °F (50 °C) operational 50/60 Hz
    [Ui] rated insulation voltage
    600 V control circuit conforming to CSA C22.2 No 14
    600 V power circuit certifications UL 508 conforming to CSA C22.2 No 14
    690 V control circuit conforming to BS 5424
    690 V control circuit conforming to IEC 60947
    690 V power circuit conforming to BS 5424
    690 V power circuit conforming to IEC 60947
    690 V power circuit conforming to NF C 20-040
    750 V control circuit conforming to VDE 0110 group C
    750 V power circuit conforming to VDE 0110 group C
    [Uimp] rated impulse withstand voltage
    8 kV
    mounting support
    Plate
    Rail
    flame retardance
    Class C2 conforming to NF F 16-101
    Class C2 conforming to NF F 16-102
    V1 conforming to UL 94
    tightening torque
    Power circuit: - on screw clamp terminal - with screwdriver flat Ø 6 mm
    Power circuit: - on screw clamp terminal - with screwdriver Philips No 2
    System Voltage
    <= 690 V AC <= 400 Hz power circuit
    [Ith] conventional free air thermal current
    10 A at <= 122 °F (50 °C) control circuit
    20 A at <= 122 °F (50 °C) power circuit
    Irms rated making capacity
    110 A at 690 V AC control circuit conforming to IEC 60947
    110 A at 690 V AC power circuit conforming to IEC 60947
    110 A at 690 V AC power circuit conforming to NF C 63-110
    rated breaking capacity
    110 A at 220...230 V power circuit conforming to IEC 60947
    110 A at 220...230 V power circuit conforming to NF C 63-110
    110 A at 380...400 V power circuit conforming to IEC 60947
    110 A at 380...400 V power circuit conforming to NF C 63-110
    110 A at 415 V power circuit conforming to IEC 60947
    110 A at 415 V power circuit conforming to NF C 63-110
    110 A at 440 V power circuit conforming to IEC 60947
    110 A at 440 V power circuit conforming to NF C 63-110
    70 A at 660...690 V power circuit conforming to IEC 60947
    70 A at 660...690 V power circuit conforming to NF C 63-110
    80 A at 500 V power circuit conforming to IEC 60947
    80 A at 500 V power circuit conforming to NF C 63-110
    associated fuse rating
    10 A gG control circuit conforming to IEC 60947
    10 A gG control circuit conforming to VDE 0660
    25 A gG at <= 440 V power circuit
    average impedance
    3 mOhm at 50 Hz - Ith 20 A power circuit
    inrush power in VA
    30 VA at 68 °F (20 °C)
    hold-in power consumption in VA
    4.5 VA at 68 °F (20 °C) 50/60 Hz
    operating time
    10...20 ms between energisation of coil and closing of NO contact
    10...20 ms coil de-energisation and NO opening
    15...25 ms coil de-energisation and NC opening
    5...15 ms coil energisation and NC opening
    safety reliability level
    B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    mechanical durability
    10000000 cycles
    operating rate
    3600 cyc/h
    minimum switching current
    5 mA control circuit
    minimum switching voltage
    17 V control circuit
    insulation resistance
    > 10 MOhm control circuit
    height
    2.28 in (58 mm)
    width
    1.77 in (45 mm)
    depth
    2.24 in (57 mm)
    product weight
    0.4 lb(US) (0.18 kg)
    Environment
    standards
    BS 5424
    IEC 60947
    NF C 63-110
    VDE 0660
    product certifications
    CSA
    GOST
    UL
    IP degree of protection
    IP2x conforming to VDE 0106
    protective treatment
    TC conforming to IEC 60068
    ambient air temperature for operation
    -13...122 °F (-25...50 °C)
    ambient air temperature for storage
    -58...176 °F (-50...80 °C)
    operating altitude
    6561.68 ft (2000 m) without derating in temperature
    fire resistance
    1562 °F (850 °C) conforming to IEC 60695-2-1
    shock resistance
    10 gn contactor closed
    6 gn contactor opened
    vibration resistance
    2 gn 5...300 Hz contactor opened
    4 gn 5...300 Hz contactor closed
    heat dissipation
    1.3 W at 50/60 Hz control circuit
    Ordering and shipping details
    Category
    22326 - CTR,K-LINE,AC,OPEN,NONREV
    Discount Schedule
    I12
    GTIN
    003389110490206
    Nbr. of units in pkg.
    30
    Package weight(Lbs)
    0.01
    Returnability
    N
    Country of origin
    FR
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • French
    Catalog
    Date
    Size
    Add to My Documents
    Date 10/31/18
    Size 102.7 MB
    Data Bulletin
    Date
    Size
    Add to My Documents
    Date 3/9/18
    Size 1.5 MB
    CAD
    Date
    Size
    Add to My Documents
    CONTACTOR
    Date 10/25/18
    Size 519.8 KB
    Date 10/25/18
    Size 257.4 KB
    Date 10/25/18
    Size 759.2 KB
    Certificate
    Date
    Size
    Add to My Documents
    Date 7/14/18
    Size 747.3 KB
    REACh Declaration
    Date
    Size
    Add to My Documents
    RoHs Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.