    Range: TeSys D Contactors

    Contactors

    LC1D80P7

    Schneider Eletric LC1D80P7 Picture
    Range: TeSys D Contactors

    Contactors

    LC1D80P7

    TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A - 230 V AC 50/60 Hz coil

    Show more characteristics >
    • Product availability
      Stock - Normally stocked in distribution facility
    • Price
      363.00 USD
    Add to My Favorites Remove from My Favorites

    • Main
      range
      TeSys
      product name
      TeSys D
      product or component type
      Contactor
      device short name
      LC1D
      contactor application
      Motor control
      Resistive load
      utilisation category
      AC-3
      AC-1
      AC-4
      poles description
      3P
      pole contact composition
      3 NO
      System Voltage
      <= 690 V AC power circuit
      <= 300 V DC 25...400 Hz power circuit
      [Ie] rated operational current
      125 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
      80 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit
      motor power kW
      22 kW at 220...230 V AC 50/60 Hz AC-3
      37 kW at 380...400 V AC 50/60 Hz AC-3
      45 kW at 660...690 V AC 50/60 Hz AC-3
      45 kW at 415...440 V AC 50/60 Hz AC-3
      55 kW at 500 V AC 50/60 Hz AC-3
      45 kW at 1000 V AC 50/60 Hz AC-3
      15 kW at 400 V AC 50/60 Hz AC-4
      motor power hp
      20 hp at 200/208 V AC 50/60 Hz 3 phases motors
      7.5 hp at 115 V AC 50/60 Hz 1 phase motors
      15 hp at 230/240 V AC 50/60 Hz 1 phase motors
      25 hp at 230/240 V AC 50/60 Hz 3 phases motors
      60 hp at 460/480 V AC 50/60 Hz 3 phases motors
      60 hp at 575/600 V AC 50/60 Hz 3 phases motors
      control circuit type
      AC 50/60 Hz
      [Uc] control circuit voltage
      230 V AC 50/60 Hz
      auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      Conforming to IEC 60947
      overvoltage category
      III
      [Ith] conventional free air thermal current
      125 A at <= 140 °F (60 °C) power circuit
      10 A at <= 140 °F (60 °C) signalling circuit
      Irms rated making capacity
      1100 A at 440 V power circuit conforming to IEC 60947
      140 A AC signalling circuit conforming to IEC 60947-5-1
      250 A DC signalling circuit conforming to IEC 60947-5-1
      rated breaking capacity
      1100 A at 440 V power circuit conforming to IEC 60947
      [Icw] rated short-time withstand current
      135 A <= 104 °F (40 °C) 10 min power circuit
      100 A 1 s signalling circuit
      120 A 500 ms signalling circuit
      140 A 100 ms signalling circuit
      640 A <= 104 °F (40 °C) 10 s power circuit
      990 A <= 104 °F (40 °C) 1 s power circuit
      320 A <= 104 °F (40 °C) 1 min power circuit
      associated fuse rating
      160 A gG at <= 690 V coordination type 2 power circuit
      200 A gG at <= 690 V coordination type 1 power circuit
      10 A gG signalling circuit conforming to IEC 60947-5-1
      average impedance
      0.8 mOhm at 50 Hz - Ith 125 A power circuit
      [Ui] rated insulation voltage
      1000 V power circuit conforming to IEC 60947-4-1
      600 V power circuit certifications CSA
      600 V power circuit certifications UL
      690 V signalling circuit conforming to IEC 60947-1
      600 V signalling circuit certifications CSA
      600 V signalling circuit certifications UL
      electrical durability
      0.8 Mcycles 125 A AC-1 at Ue <= 440 V
      1.5 Mcycles 80 A AC-3 at Ue <= 440 V
      power dissipation per pole
      5.1 W AC-3
      12.5 W AC-1
      protective cover
      With
      mounting support
      Rail
      Plate
      standards
      CSA C22.2 No 14
      EN 60947-4-1
      EN 60947-5-1
      IEC 60947-4-1
      IEC 60947-5-1
      UL 508
      product certifications
      DNV
      GOST
      RINA
      BV
      GL
      CSA
      CCC
      LROS (Lloyds register of shipping)
      UL
      connections - terminals
      Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
      Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
      Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
      Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
      Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
      Control circuit: screw clamp terminals 1 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
      Power circuit: connector 1 cable(s) 0.01...0.08 in² (4...50 mm²) - cable stiffness: flexible - without cable end
      Power circuit: connector 2 cable(s) 0.01...0.04 in² (4...25 mm²) - cable stiffness: flexible - without cable end
      Power circuit: connector 1 cable(s) 0.01...0.08 in² (4...50 mm²) - cable stiffness: flexible - with cable end
      Power circuit: connector 2 cable(s) 0.01...0.02 in² (4...16 mm²) - cable stiffness: flexible - with cable end
      Power circuit: connector 1 cable(s) 0.01...0.08 in² (4...50 mm²) - cable stiffness: solid - without cable end
      Power circuit: connector 2 cable(s) 0.01...0.04 in² (4...25 mm²) - cable stiffness: solid - without cable end
      tightening torque
      Power circuit: 79.65 lbf.in (9 N.m) - on connector - with screwdriver flat Ø 6 to Ø 8 mm
      Power circuit: 79.65 lbf.in (9 N.m) - on connector hexagonal 0.16 in (4 mm)
      Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
      Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminals - with screwdriver Philips No 2
      operating time
      20...35 ms closing
      6...20 ms opening
      safety reliability level
      B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
      B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
      mechanical durability
      4 Mcycles
      operating rate
      3600 cyc/h at <= 140 °F (60 °C)
      Complementary
      coil technology
      Without built-in suppressor module
      control circuit voltage limits
      0.85...1.1 Uc operational at 131 °F (55 °C), AC 60 Hz
      0.3...0.6 Uc drop-out at 131 °F (55 °C), AC 50/60 Hz
      0.8...1.1 Uc operational at 55 °C, AC 50 Hz
      inrush power in VA
      245 VA at 68 °F (20 °C) (cos ϕ 0.75) 60 Hz
      245 VA at 68 °F (20 °C) (cos ϕ 0.75) 50 Hz
      hold-in power consumption in VA
      26 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
      26 VA at 68 °F (20 °C) (cos ϕ 0.3) 50 Hz
      heat dissipation
      6...10 W at 50/60 Hz
      auxiliary contacts type
      Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
      Type mirror contact (1 NC) conforming to IEC 60947-4-1
      signalling circuit frequency
      25...400 Hz
      minimum switching current
      5 mA signalling circuit
      minimum switching voltage
      17 V signalling circuit
      non-overlap time
      1.5 ms on de-energisation (between NC and NO contact)
      1.5 ms on energisation (between NC and NO contact)
      insulation resistance
      > 10 MOhm signalling circuit
      Environment
      IP degree of protection
      IP20 front face conforming to IEC 60529
      protective treatment
      TH conforming to IEC 60068-2-30
      pollution degree
      3
      ambient air temperature for operation
      23...140 °F (-5...60 °C)
      ambient air temperature for storage
      -76...176 °F (-60...80 °C)
      permissible ambient air temperature around the device
      -40...158 °F (-40...70 °C) at Uc
      operating altitude
      9842.52 ft (3000 m) without derating in temperature
      fire resistance
      1562 °F (850 °C) conforming to IEC 60695-2-1
      flame retardance
      V1 conforming to UL 94
      mechanical robustness
      Vibrations contactor open 2 Gn, 5...300 Hz
      Shocks contactor open 8 Gn for 11 ms
      Vibrations contactor closed 3 Gn, 5...300 Hz
      Shocks contactor closed 10 Gn for 11 ms
      height
      5 in (127 mm)
      width
      3.35 in (85 mm)
      depth
      5.12 in (130 mm)
      product weight
      3.51 lb(US) (1.59 kg)
      Ordering and shipping details
      Category
      22345 - CTR,D-LINE,OPEN,NONREV-NEW
      Discount Schedule
      I12
      GTIN
      00785901799603
      Nbr. of units in pkg.
      1
      Package weight(Lbs)
      3.48
      Returnability
      Y
      Country of origin
      CZ
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  0701  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Available
      Product end of life instructions
      Need no specific recycling operations
      Contractual warranty
      Warranty period
      18 months
    • Documents and Downloads

      Language
      • English
      • Spanish
      Catalog
      Date
      Size
      Add to My Documents
      Date 8/13/18
      Size 102.7 MB
      Data Bulletin
      Date
      Size
      Add to My Documents
      Date 3/9/18
      Size 1.5 MB
      CAD
      Date
      Size
      Add to My Documents
      CONTACTOR
      Date 3/12/18
      Size 310.2 KB
      Date 3/12/18
      Size 266.9 KB
      Date 3/12/18
      Size 628.2 KB
      IEC Contactor, 80A, 3 Pole, D-Line (TESYS)
      Certificate
      Date
      Size
      Add to My Documents
      Date 2/8/18
      Size 1.9 MB
      Instruction Sheet
      Date
      Size
      Add to My Documents
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
    • Dimensions Drawings

      Dimensions


      (1)
      Minimum electrical clearance

      LC1

      D80

      D95

      a

      85

      85

      b1

      with LA4 D●2

      135

      135

      with LA4 DB3 or LAD 4BB3

      135

      with LA4 DF, DT

      142

      142

      with LA4 DM, DW, DL

      150

      150

      c

      without cover or add-on blocks

      125

      125

      with cover, without add-on blocks

      130

      130

      c1

      with LAD N (1 contact)

      150

      150

      with LAD N or C (2 or 4 contacts)

      158

      158

      c2

      with LA6 DK10, LAD 6DK

      170

      170

      c3

      with LAD T, R, S

      178

      178

      with LAD T, R, S and sealing cover

      182

      182


    • Connections and Schema

      Wiring



    • Motor Starter BOM

      Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 37 kW and 415 VAC

      Motor power

      (kW)

      ICU

      (kA)

      Breaker

      Contactor (*)

      37

      36


      GV7RE80


      LC1D80P7

      37

      15


      GV3ME80


      LC1D80P7

      Non contractual pictures.

      Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.