    Schneider Eletric LC1D25P7 Picture

    Range: TeSys D Contactors

    Contactors

    LC1D25P7

    Schneider Eletric LC1D25P7 Picture
    Range: TeSys D Contactors

    Contactors

    LC1D25P7

    TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 230 V AC coil

    Show more characteristics >
    • Product availability
      Stock - Normally stocked in distribution facility
    • Price
      151.00 USD
    Add to My Favorites Remove from My Favorites

    • Main
      range of product
      TeSys D
      range
      TeSys
      product name
      TeSys D
      product or component type
      Contactor
      device short name
      LC1D
      contactor application
      Motor control
      Resistive load
      utilisation category
      AC-1
      AC-3
      AC-4
      poles description
      3P
      pole contact composition
      3 NO
      System Voltage
      <= 300 V DC power circuit
      <= 690 V AC 25...400 Hz power circuit
      [Ie] rated operational current
      25 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit
      40 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
      motor power kW
      11 kW at 380...400 V AC 50/60 Hz AC-3
      15 kW at 500 V AC 50/60 Hz AC-3
      15 kW at 660...690 V AC 50/60 Hz AC-3
      5.5 kW at 220...230 V AC 50/60 Hz AC-3
      11 kW at 415...440 V AC 50/60 Hz AC-3
      5.5 kW at 400 V AC 50/60 Hz AC-4
      motor power hp
      2 hp at 115 V AC 50/60 Hz 1 phase motors
      7.5 hp at 200/208 V AC 50/60 Hz 3 phases motors
      3 hp at 230/240 V AC 50/60 Hz 1 phase motors
      7.5 hp at 230/240 V AC 50/60 Hz 3 phases motors
      15 hp at 460/480 V AC 50/60 Hz 3 phases motors
      20 hp at 575/600 V AC 50/60 Hz 3 phases motors
      control circuit type
      AC 50/60 Hz
      [Uc] control circuit voltage
      230 V AC 50/60 Hz
      auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      overvoltage category
      III
      [Ith] conventional free air thermal current
      40 A at <= 140 °F (60 °C) power circuit
      10 A at <= 140 °F (60 °C) signalling circuit
      Irms rated making capacity
      450 A at 440 V power circuit conforming to IEC 60947
      140 A AC signalling circuit conforming to IEC 60947-5-1
      250 A DC signalling circuit conforming to IEC 60947-5-1
      rated breaking capacity
      450 A at 440 V power circuit conforming to IEC 60947
      [Icw] rated short-time withstand current
      120 A <= 104 °F (40 °C) 1 min power circuit
      240 A <= 104 °F (40 °C) 10 s power circuit
      380 A <= 104 °F (40 °C) 1 s power circuit
      50 A <= 104 °F (40 °C) 10 min power circuit
      100 A 1 s signalling circuit
      120 A 500 ms signalling circuit
      140 A 100 ms signalling circuit
      associated fuse rating
      40 A gG at <= 690 V coordination type 2 power circuit
      63 A gG at <= 690 V coordination type 1 power circuit
      10 A gG signalling circuit conforming to IEC 60947-5-1
      average impedance
      2 mOhm at 50 Hz - Ith 40 A power circuit
      [Ui] rated insulation voltage
      600 V power circuit certifications CSA
      600 V power circuit certifications UL
      690 V power circuit conforming to IEC 60947-4-1
      690 V signalling circuit conforming to IEC 60947-1
      600 V signalling circuit certifications CSA
      600 V signalling circuit certifications UL
      electrical durability
      1.65 Mcycles 25 A AC-3 at Ue <= 440 V
      1.4 Mcycles 40 A AC-1 at Ue <= 440 V
      power dissipation per pole
      3.2 W AC-1
      1.25 W AC-3
      protective cover
      With
      mounting support
      Plate
      Rail
      standards
      CSA C22.2 No 14
      EN 60947-4-1
      EN 60947-5-1
      IEC 60947-4-1
      IEC 60947-5-1
      UL 508
      product certifications
      BV
      CCC
      CSA
      DNV
      GL
      GOST
      LROS (Lloyds register of shipping)
      RINA
      UL
      connections - terminals
      Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
      Power circuit: screw clamp terminals 1 cable(s) 0...0.02 in² (1.5...10 mm²) - cable stiffness: solid - without cable end
      Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
      Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
      Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with cable end
      Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
      Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
      Power circuit: screw clamp terminals 1 cable(s) 0...0.02 in² (2.5...10 mm²) - cable stiffness: flexible - without cable end
      Power circuit: screw clamp terminals 2 cable(s) 0...0.02 in² (2.5...10 mm²) - cable stiffness: flexible - without cable end
      Power circuit: screw clamp terminals 1 cable(s) 0...0.02 in² (1...10 mm²) - cable stiffness: flexible - with cable end
      Power circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...6 mm²) - cable stiffness: flexible - with cable end
      Power circuit: screw clamp terminals 2 cable(s) 0...0.02 in² (2.5...10 mm²) - cable stiffness: solid - without cable end
      tightening torque
      Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
      Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver Philips No 2
      Power circuit: 22.12 lbf.in (2.5 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
      Power circuit: 22.12 lbf.in (2.5 N.m) - on screw clamp terminals - with screwdriver Philips No 2
      operating time
      4...19 ms opening
      12...22 ms closing
      safety reliability level
      B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
      B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
      mechanical durability
      15 Mcycles
      operating rate
      3600 cyc/h at <= 140 °F (60 °C)
      Complementary
      coil technology
      Without built-in suppressor module
      control circuit voltage limits
      0.3...0.6 Uc drop-out at 140 °F (60 °C), AC 50/60 Hz
      0.8...1.1 Uc operational at 140 °F (60 °C), AC 50 Hz
      0.85...1.1 Uc operational at 140 °F (60 °C), AC 60 Hz
      inrush power in VA
      70 VA at 68 °F (20 °C) (cos ϕ 0.75) 60 Hz
      70 VA at 68 °F (20 °C) (cos ϕ 0.75) 50 Hz
      hold-in power consumption in VA
      7.5 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
      7 VA at 68 °F (20 °C) (cos ϕ 0.3) 50 Hz
      heat dissipation
      2...3 W at 50/60 Hz
      auxiliary contacts type
      Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
      Type mirror contact (1 NC) conforming to IEC 60947-4-1
      signalling circuit frequency
      25...400 Hz
      minimum switching current
      5 mA signalling circuit
      minimum switching voltage
      17 V signalling circuit
      non-overlap time
      1.5 ms on energisation between NC and NO contact
      1.5 ms on de-energisation between NC and NO contact
      insulation resistance
      > 10 MOhm signalling circuit
      contact compatibility
      M2
      compatibility code
      LC1D
      power range
      7...11 kW 380...440 V 3 phases
      7...11 kW 480...500 V 3 phases
      4...6 kW 200...240 V 3 phases
      motor starter type
      Direct on-line contactor
      contactor coil voltage
      230 V AC standard
      Environment
      IP degree of protection
      IP20 front face conforming to IEC 60529
      protective treatment
      TH conforming to IEC 60068-2-30
      pollution degree
      3
      ambient air temperature for operation
      23...140 °F (-5...60 °C)
      ambient air temperature for storage
      -76...176 °F (-60...80 °C)
      permissible ambient air temperature around the device
      -40...158 °F (-40...70 °C) at Uc
      operating altitude
      9842.52 ft (3000 m) without derating in temperature
      fire resistance
      1562 °F (850 °C) conforming to IEC 60695-2-1
      flame retardance
      V1 conforming to UL 94
      mechanical robustness
      Vibrations contactor open 2 Gn, 5...300 Hz
      Vibrations contactor closed 4 Gn, 5...300 Hz
      Shocks contactor closed 15 Gn for 11 ms
      Shocks contactor open 8 Gn for 11 ms
      height
      3.35 in (85 mm)
      width
      1.77 in (45 mm)
      depth
      3.62 in (92 mm)
      product weight
      0.82 lb(US) (0.37 kg)
      Ordering and shipping details
      Category
      22345 - CTR,D-LINE,OPEN,NONREV-NEW
      Discount Schedule
      I12
      GTIN
      00785901686156
      Nbr. of units in pkg.
      1
      Package weight(Lbs)
      0.92000000000000004
      Returnability
      Y
      Country of origin
      ID
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  0627  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Available
      Product end of life instructions
      Available
      Contractual warranty
      Warranty period
      18 months
    • Documents and Downloads

      Language
      • ALL
      • English
      Data Bulletin
      Date
      Size
      Add to My Documents
      Date 3/9/18
      Size 1.5 MB
      CAD
      Date
      Size
      Add to My Documents
      CONTACTOR
      Date 3/12/18
      Size 441.6 KB
      Date 3/12/18
      Size 229.9 KB
      Date 3/12/18
      Size 436.5 KB
      IEC Contactor, 25-32A, 3 Pole, D-Line (TESYS)
      Certificate
      Date
      Size
      Add to My Documents
      Date 11/10/17
      Size 2.7 MB
      Date 11/10/17
      Size 1.5 MB
      Instruction Sheet
      Date
      Size
      Add to My Documents
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
    • Dimensions Drawings

      Dimensions


      (1)
      Including LAD 4BB
      (2)
      Minimum electrical clearance

      LC1

      D25…D38 (3-pole)

      b

      without add-on blocks

      85

      b1

      with LAD 4BB

      98

      with LA4 D●2

      114(1)

      with LA4 DF, DT

      123(1)

      with LA4 DW, DL

      130(1)

      c

      without cover or add-on blocks

      90

      with cover, without add-on blocks

      92

      c1

      with LAD N or C (2 or 4 contacts)

      123

      c2

      with LA6 DK10, LAD 6K10

      135

      c3

      with LAD T, R, S

      143

      with LAD T, R, S and sealing cover

      147

      (1)

      Including LAD 4BB.


    • Connections and Schema

      Wiring



    • Motor Starter BOM

      Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power from 9 to 11 kW and 415 VAC

      Motor power

      (kW)

      ICU

      (kA)

      Breaker

      Contactor (*)

      9

      15


      GV2ME21


      LC1D25P7

      11

      15


      GV2ME22


      LC1D25P7

      Non contractual pictures.

      Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.