TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 220 V AC 60 Hz coil

Show more characteristics >
  • Product availability
    Non-Stock - Not normally stocked in distribution facility
Add to My Products Remove from My Products

  • Main
    range
    TeSys
    product name
    TeSys D
    product or component type
    Contactor
    device short name
    LC1D
    contactor application
    Motor control
    Resistive load
    utilisation category
    AC-1
    AC-3
    AC-4
    poles description
    3P
    power pole contact composition
    3 NO
    System Voltage
    <= 300 V DC power circuit
    <= 1000 V AC 25...400 Hz power circuit
    [Ie] rated operational current
    200 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
    115 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit
    motor power kW
    55 kW at 380...400 V AC 50/60 Hz AC-3
    75 kW at 500 V AC 50/60 Hz AC-3
    80 kW at 660...690 V AC 50/60 Hz AC-3
    30 kW at 220...230 V AC 50/60 Hz AC-3
    59 kW at 415...440 V AC 50/60 Hz AC-3
    65 kW at 1000 V AC 50/60 Hz AC-3
    18.5 kW at 400 V AC 50/60 Hz AC-4
    motor power HP (UL / CSA)
    30 hp at 200/208 V AC 50/60 Hz 3 phases motors
    40 hp at 230/240 V AC 50/60 Hz 3 phases motors
    75 hp at 460/480 V AC 50/60 Hz 3 phases motors
    100 hp at 575/600 V AC 50/60 Hz 3 phases motors
    control circuit type
    AC 60 Hz
    [Uc] control circuit voltage
    220 V AC 60 Hz
    auxiliary contact composition
    1 NO + 1 NC
    [Uimp] rated impulse withstand voltage
    Conforming to IEC 60947
    overvoltage category
    III
    [Ith] conventional free air thermal current
    200 A at <= 140 °F (60 °C) power circuit
    Irms rated making capacity
    1260 A at 440 V power circuit conforming to IEC 60947
    140 A AC signalling circuit conforming to IEC 60947-5-1
    250 A DC signalling circuit conforming to IEC 60947-5-1
    rated breaking capacity
    1100 A at 440 V power circuit conforming to IEC 60947
    [Icw] rated short-time withstand current
    1100 A <= 104 °F (40 °C) 1 s power circuit
    100 A 1 s signalling circuit
    120 A 500 ms signalling circuit
    140 A 100 ms signalling circuit
    250 A <= 104 °F (40 °C) 10 min power circuit
    550 A <= 104 °F (40 °C) 1 min power circuit
    950 A <= 104 °F (40 °C) 10 s power circuit
    associated fuse rating
    200 A gG at <= 690 V coordination type 2 power circuit
    250 A gG at <= 690 V coordination type 1 power circuit
    10 A gG signalling circuit
    average impedance
    0.6 mOhm at 50 Hz - Ith 200 A power circuit
    [Ui] rated insulation voltage
    1000 V power circuit conforming to IEC 60947-4-1
    600 V power circuit certifications CSA
    600 V power circuit certifications UL
    690 V signalling circuit conforming to IEC 60947-1
    600 V signalling circuit certifications CSA
    600 V signalling circuit certifications UL
    electrical durability
    0.8 Mcycles 200 A AC-1 at Ue <= 440 V
    0.95 Mcycles 115 A AC-3 at Ue <= 440 V
    power dissipation per pole
    24 W AC-1
    7.9 W AC-3
    safety cover
    With
    mounting support
    Plate
    Rail
    standards
    CSA C22.2 No 14
    EN 60947-4-1
    EN 60947-5-1
    IEC 60947-4-1
    IEC 60947-5-1
    UL 508
    product certifications
    BV
    CCC
    CSA
    DNV
    GL
    GOST
    LROS (Lloyds register of shipping)
    RINA
    UL
    connections - terminals
    Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - without cable end
    Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
    Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: solid - without cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - without cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: solid - without cable end
    Power circuit: connector 1 cable(s) 0.02...0.19 in² (10...120 mm²) - cable stiffness: flexible - without cable end
    Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50 mm²) - cable stiffness: flexible - without cable end
    Power circuit: connector 1 cable(s) 0.02...0.19 in² (10...120 mm²) - cable stiffness: flexible - with cable end
    Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50 mm²) - cable stiffness: flexible - with cable end
    Power circuit: connector 1 cable(s) 0.02...0.19 in² (10...120 mm²) - cable stiffness: solid - without cable end
    Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50 mm²) - cable stiffness: solid - without cable end
    tightening torque
    Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminals - with screwdriver Philips No 2
    Power circuit: 106.19 lbf.in (12 N.m) - on connector hexagonal 0.16 in (4 mm)
    operating time
    6...20 ms opening
    20...50 ms closing
    safety reliability level
    B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    mechanical durability
    8 Mcycles
    operating rate
    2400 cyc/h at <= 140 °F (60 °C)
    Complementary
    coil technology
    Without built-in suppressor module
    control circuit voltage limits
    0.85...1.1 Uc operational at 131 °F (55 °C), AC 60 Hz
    0.3...0.6 Uc drop-out at 131 °F (55 °C), AC 60 Hz
    inrush power in VA
    300 VA at 68 °F (20 °C) (cos ϕ 0.8) 60 Hz
    hold-in power consumption in VA
    22 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
    heat dissipation
    3...8 W at 60 Hz
    auxiliary contacts type
    Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
    Type mirror contact (1 NC) conforming to IEC 60947-4-1
    signalling circuit frequency
    25...400 Hz
    minimum switching current
    5 mA signalling circuit
    minimum switching voltage
    17 V signalling circuit
    non-overlap time
    1.5 ms on de-energisation (between NC and NO contact)
    1.5 ms on energisation (between NC and NO contact)
    insulation resistance
    > 10 MOhm signalling circuit
    Environment
    IP degree of protection
    IP20 front face conforming to IEC 60529
    protective treatment
    TH conforming to IEC 60068-2-30
    pollution degree
    3
    ambient air temperature for operation
    23...140 °F (-5...60 °C)
    ambient air temperature for storage
    -76...176 °F (-60...80 °C)
    permissible ambient air temperature around the device
    -40...158 °F (-40...70 °C) at Uc
    operating altitude
    9842.52 ft (3000 m) without derating
    fire resistance
    1562 °F (850 °C) conforming to IEC 60695-2-1
    flame retardance
    V1 conforming to UL 94
    mechanical robustness
    Vibrations contactor open 2 Gn, 5...300 Hz
    Vibrations contactor closed 4 Gn, 5...300 Hz
    Shocks contactor closed 15 Gn for 11 ms
    Shocks contactor open 6 Gn for 11 ms
    height
    6.22 in (158 mm)
    width
    4.72 in (120 mm)
    depth
    5.35 in (136 mm)
    product weight
    5.51 lb(US) (2.5 kg)
    Ordering and shipping details
    Category
    22345 - CTR,D-LINE,OPEN,NONREV-NEW
    Discount Schedule
    I12
    GTIN
    003389110377163
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    5.2999999999999998
    Returnability
    N
    Country of origin
    CZ
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Available
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Portuguese
    • Russian
    • French
    • Italian
    • German
    • Chinese
    CAD
    Date
    Size
    Add to My Documents
    CONTACTOR (Version 1.0)
    Date 6/25/18
    Size 733.3 KB
    Date 6/25/18
    Size 573.1 KB
    Certificate
    Date
    Size
    Add to My Documents
    CCC TeSys D - LC.D115-150, Czech Republic (Version 1.0)
    CB TeSys D - LC1D115-150 (Version 1.0)
    Date 11/10/17
    Size 263.8 KB
    Instruction Sheet
    Date
    Size
    Add to My Documents
    LC1/LC2 D115 D150 Contactors / Reversing contactors (Version 12)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    PEP - TeSys D LC1D115 to D150 contactors (Version 2.0)
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.