USA

Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

Schneider Eletric LC1D115004T7 Picture
Discontinued

Schneider Eletric LC1D115004T7 Picture
Discontinued

TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 200 A - 480 V AC 50/60 Hz coil

Show more characteristics >
LC1D115004T7  has not been replaced. Please contact your customer care center for more information.
  • Price
    630.00 USD
Add to My Products Remove from My Products

  • Main
    range
    TeSys
    product name
    TeSys D
    product or component type
    Contactor
    device short name
    LC1D
    contactor application
    Resistive load
    utilisation category
    AC-1
    poles description
    4P
    power pole contact composition
    4 NO
    System Voltage
    <= 460 V DC power circuit
    <= 1000 V AC 25...400 Hz power circuit
    [Ie] rated operational current
    200 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
    control circuit type
    AC 50/60 Hz
    [Uc] control circuit voltage
    480 V AC 50/60 Hz
    [Uimp] rated impulse withstand voltage
    Conforming to IEC 60947
    overvoltage category
    III
    [Ith] conventional free air thermal current
    200 A at <= 140 °F (60 °C) power circuit
    Irms rated making capacity
    1260 A at 440 V power circuit conforming to IEC 60947
    rated breaking capacity
    1100 A at 440 V power circuit conforming to IEC 60947
    [Icw] rated short-time withstand current
    1100 A <= 104 °F (40 °C) 1 s power circuit
    250 A <= 104 °F (40 °C) 10 min power circuit
    550 A <= 104 °F (40 °C) 1 min power circuit
    950 A <= 104 °F (40 °C) 10 s power circuit
    associated fuse rating
    200 A gG at <= 690 V coordination type 2 power circuit
    250 A gG at <= 690 V coordination type 1 power circuit
    average impedance
    0.6 mOhm at 50 Hz - Ith 200 A power circuit
    [Ui] rated insulation voltage
    1000 V power circuit conforming to IEC 60947-4-1
    600 V power circuit certifications CSA
    600 V power circuit certifications UL
    electrical durability
    0.8 Mcycles 200 A AC-1 at Ue <= 440 V
    power dissipation per pole
    24 W AC-1
    safety cover
    With
    mounting support
    Plate
    Rail
    standards
    CSA C22.2 No 14
    EN 60947-4-1
    EN 60947-5-1
    IEC 60947-4-1
    IEC 60947-5-1
    UL 508
    product certifications
    BV
    CCC
    CSA
    DNV
    GL
    GOST
    LROS (Lloyds register of shipping)
    RINA
    UL
    connections - terminals
    Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - without cable end
    Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
    Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: solid - without cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - without cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: solid - without cable end
    Power circuit: connector 1 cable(s) 0.02...0.19 in² (10...120 mm²) - cable stiffness: flexible - without cable end
    Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50 mm²) - cable stiffness: flexible - without cable end
    Power circuit: connector 1 cable(s) 0.02...0.19 in² (10...120 mm²) - cable stiffness: flexible - with cable end
    Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50 mm²) - cable stiffness: flexible - with cable end
    Power circuit: connector 1 cable(s) 0.02...0.19 in² (10...120 mm²) - cable stiffness: solid - without cable end
    Power circuit: connector 2 cable(s) 0.02...0.08 in² (10...50 mm²) - cable stiffness: solid - without cable end
    tightening torque
    Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminals - with screwdriver Philips No 2
    Power circuit: 106.19 lbf.in (12 N.m) - on connector hexagonal 0.16 in (4 mm)
    operating time
    6...20 ms opening
    20...50 ms closing
    safety reliability level
    B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    mechanical durability
    8 Mcycles
    operating rate
    2400 cyc/h at <= 140 °F (60 °C)
    Complementary
    coil technology
    Built-in bidirectional peak limiting diode suppressor
    control circuit voltage limits
    0.3...0.5 Uc drop-out at 131 °F (55 °C), AC 50/60 Hz
    0.8...1.15 Uc operational at 131 °F (55 °C), AC 50/60 Hz
    inrush power in VA
    280...350 VA at 68 °F (20 °C) (cos ϕ 0.8) 60 Hz
    280...350 VA at 68 °F (20 °C) (cos ϕ 0.8) 50 Hz
    hold-in power consumption in VA
    2...18 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
    2...18 VA at 68 °F (20 °C) (cos ϕ 0.3) 50 Hz
    heat dissipation
    3...8 W at 50/60 Hz
    Environment
    IP degree of protection
    IP20 front face conforming to IEC 60529
    protective treatment
    TH conforming to IEC 60068-2-30
    pollution degree
    3
    ambient air temperature for operation
    23...140 °F (-5...60 °C)
    ambient air temperature for storage
    -76...176 °F (-60...80 °C)
    permissible ambient air temperature around the device
    -40...158 °F (-40...70 °C) at Uc
    operating altitude
    9842.52 ft (3000 m) without derating
    fire resistance
    1562 °F (850 °C) conforming to IEC 60695-2-1
    flame retardance
    V1 conforming to UL 94
    mechanical robustness
    Vibrations contactor open 2 Gn, 5...300 Hz
    Vibrations contactor closed 4 Gn, 5...300 Hz
    Shocks contactor closed 15 Gn for 11 ms
    Shocks contactor open 6 Gn for 11 ms
    height
    6.22 in (158 mm)
    width
    5.91 in (150 mm)
    depth
    5.2 in (132 mm)
    product weight
    6.31 lb(US) (2.86 kg)
    Ordering and shipping details
    Category
    22345 - CTR,D-LINE,OPEN,NONREV-NEW
    Discount Schedule
    I12
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    6.1000000000000005
    Returnability
    N
    Country of origin
    CZ
    Offer Sustainability
    RoHS (date code: YYWW)
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.