    Range: Soft Start - Altistart 22

    Soft starters

    ATS22C48Q

    Schneider Eletric ATS22C48Q Picture
    Range: Soft Start - Altistart 22

    Soft starters

    ATS22C48Q

    soft starter-ATS22-control 220V-power 230V(132kW)/400...440V(250kW)

    Show more characteristics >
    • Product availability
      Non-Stock - Not normally stocked in distribution facility
    • Price
      4263.00 USD
    Add to My Favorites Remove from My Favorites

    • Main
      range of product
      Altistart 22
      product or component type
      Soft starter
      product destination
      Asynchronous motors
      product specific application
      Pumps and fans
      component name
      ATS22
      Phase
      3 phases
      [Us] rated supply voltage
      230...440 V - 15...10 %
      motor power kW
      132 kW 230 V
      250 kW 400 V
      250 kW 440 V
      factory setting current
      437 A
      power dissipation in W
      218 W for standard applications
      utilisation category
      AC-53A
      type of start
      Start with torque control (current limited to 3.5 In)
      IcL starter rating
      480 A connection in the motor supply line for standard applications
      IP degree of protection
      IP00
      Complementary
      assembly style
      With heat sink
      function available
      Internal bypass
      supply voltage limits
      195...484 V
      supply frequency
      50...60 Hz - 10...10 %
      network frequency
      45...66 Hz
      device connection
      In the motor supply line
      To the motor delta terminals
      [Uc] control circuit voltage
      230 V -15...10 % 50/60 Hz
      control circuit consumption
      20 W
      discrete output number
      2
      discrete output type
      Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
      Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
      minimum switching current
      100 mA 12 V DC relay outputs
      maximum switching current
      5 A 250 V AC resistive 1 relay outputs
      5 A 30 V DC resistive 1 relay outputs
      2 A 250 V AC inductive 0.4 20 ms relay outputs
      2 A 30 V DC inductive 7 ms relay outputs
      discrete input number
      3
      discrete input type
      Logic LI1, LI2, LI3 5 mA 4.3 kOhm
      discrete input voltage
      24 V <= 30 V
      discrete input logic
      Positive logic LI1, LI2, LI3 < 5 V and <= 2 mA > 11 V >= 5 mA
      output current
      0.4...1 Icl adjustable
      PTC probe input
      750 Ohm
      communication port protocol
      Modbus
      connector type
      1 RJ45
      communication data link
      Serial
      physical interface
      RS485 multidrop
      transmission rate
      4800, 9600 or 19200 bps
      installed device
      31
      protection type
      Phase failure line
      Thermal protection starter
      Thermal protection motor
      marking
      CE
      type of cooling
      Forced convection
      operating position
      Vertical +/- 10 degree
      height
      17.91 in (455 mm)
      width
      11.97 in (304 mm)
      depth
      13.37 in (339.7 mm)
      product weight
      110.23 lb(US) (50 kg)
      power range
      110...220 kW at 200...240 V 3 phases
      250...500 kW at 380...440 V 3 phases
      motor starter type
      Soft starter
      Environment
      electromagnetic compatibility
      Conducted and radiated emissions level A IEC 60947-4-2
      Damped oscillating waves level 3 IEC 61000-4-12
      Electrostatic discharge level 3 IEC 61000-4-2
      Immunity to electrical transients level 4 IEC 61000-4-4
      Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3
      Voltage/current impulse level 3 IEC 61000-4-5
      standards
      EN/IEC 60947-4-2
      product certifications
      CCC
      CSA
      C-Tick
      GOST
      UL
      vibration resistance
      1.5 mm 2...13 Hz EN/IEC 60068-2-6
      1 gn 13...200 Hz EN/IEC 60068-2-6
      shock resistance
      15 gn 11 ms EN/IEC 60068-2-27
      noise level
      56 dB
      pollution degree
      Level 2 IEC 60664-1
      relative humidity
      0...95 % without condensation or dripping water EN/IEC 60068-2-3
      ambient air temperature for operation
      14...104 °F (-10...40 °C) without derating
      > 104...< 140 °F (> 40...< 60 °C) with current derating 2.2 % per °C
      ambient air temperature for storage
      -13...158 °F (-25...70 °C)
      operating altitude
      <= 3280.84 ft (1000 m) without derating
      > 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m
      Ordering and shipping details
      Category
      22576 - ATS22 ALTISTART
      Discount Schedule
      CP1G
      GTIN
      00785901963974
      Nbr. of units in pkg.
      1
      Package weight(Lbs)
      81.400000000000006
      Returnability
      N
      Country of origin
      CN
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  0939  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Available
      Product end of life instructions
      Available
      Contractual warranty
      Warranty period
      18 months
    • Documents and Downloads

      Language
      • English
      • Spanish
      • French
      Catalog
      Date
      Size
      Add to My Documents
      Date 6/20/18
      Size 2.6 MB
      User guide
      Date
      Size
      Add to My Documents
      Date 2/8/17
      Size 458.8 KB
      Date 12/14/17
      Size 467.5 KB
      Date 5/3/17
      Size 2.9 MB
      Certificate
      Date
      Size
      Add to My Documents
      Date 4/27/18
      Size 399.4 KB
      Date 5/31/18
      Size 153 KB
      Date 6/19/18
      Size 69.4 KB
      Software - Released
      Date
      Size
      Add to My Documents
      SoMove V2.6.5 (FDT Standalone)
      Date 6/19/18
      Size 234.4 MB
      Date 6/19/18
      Size 107.1 KB
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
    • Dimensions Drawings

      Frame Size E
      Dimensions



    • Mounting and Clearance

      Precautions
      Standards

      The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.

      For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.

      DANGER

      HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

      ATS22 soft starters are open devices and must be mounted in a suitable enclosure.

      Failure to follow these instructions will result in death or serious injury.

      Air Circulation

      Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the unit.


      Overheating

      To avoid the soft starter to overheat, respect the following recommendations:

      • Mount the Altistart 22 Soft Starter within ± 10° of vertical.

      • Do not locate the Altistart 22 Soft Starter near heat radiating elements.

      • Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the ambient air immediately surrounding the soft starter. To help prevent a thermal fault, provide sufficient enclosure cooling and/or ventilation to limit the ambient temperature around the soft starter.

      • If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat generated from the bottom soft starter can adversely affect the ambient temperature around the top soft starter.


      Wall mounted or Floor-standing Enclosure with IP 23 Degree of protection
      Introduction

      To help proper air circulation in the soft starter, grilles and forced ventilation can be installed.

      Ventilation Grilles


      Forced Ventilation Unit



    • Connections and Schema

      Power Terminal
      Bar Style


      Power supply and output to motor

      Bar

      b

      40 mm (1.18 in)

      a

      5 mm (0.2 in)

      Bolt

      M12 (0.47 in)

      Cable and protective cover

      Size

      2X240 mm²

      Gauge

      2X500 MCM

      Protective cover

      LA9F703

      Tightening torque

      57 N.m

      498.75 lb.in

      Power connections, minimum required wiring section

      IEC cable

      mm² (Cu 70°C/158°F) (1)

      UL cable

      AWG (Cu 75°C/167°F) (1)

      2 X 150

      3 X 350 MCM


      230 Vac control, logic Inputs (LI) 24 Vdc, 3-wire control
      With Line Contactor, Freewheel or Controlled Stop



      230 Vac control, logic Inputs (LI) 24 Vdc, 2-wire control,freewheel stop



      Connection in the motor delta winding in series with each winding
      Wiring

      ATS22 soft starters connected to motors with the delta connections can be inserted in series in the motor windings.

      The following wiring requieres particular attention. It is documented in the Altistart 22 Soft start - soft stop unit user manual. Please contact Schneider Electric commercial organisation for further informations.


      Example

      A 400 V - 110 kW motor with a line current of 195 A (nominal current for the delta connection). The current in each winding is equal to 195/1.5 or 130 A. The rating is determined by selecting the soft starter with a permanent nominal current (ICL) just above this current.


    • Performance Curves

      Motor Thermal Protection - Cold Curves
      Curves


      A
      Class 10
      B
      Class 20
      C
      Class 30

      Trip time for a Standard Application (Class 10)

      3.5 ln

      32 s

      Trip time for a Severe Application (Class 20)

      3.5 ln

      63 s

      Trip time for a Severe Application (Class 30)

      3.5 ln

      95 s


      Motor Thermal Protection - Warm Curves
      Curves


      A
      Class 10
      B
      Class 20
      C
      Class 30

      Trip time for a Standard Application (Class 10)

      3.5 ln

      16 s

      Trip time for a Severe Application (Class 20)

      3.5 ln

      32 s

      Trip time for a Severe Application (Class 30)

      3.5 ln

      48 s


    • Motor Starter BOM

      Our Proposal: Circuit Breaker + Contactor + Soft starter for Motor Power 250 kW and 400 VAC

      Motor power

      (kW)

      ICU

      (kA)

      Breaker

      Contactor (*)

      Instantaneous auxiliary contacts

      Motor Starter

      250

      36


      LV432948


      LC1F500P7


      LADN22


      ATS22C48Q

      Non contractual pictures.

      Motor power

      kW

      Coil voltage

      VDC

      24

      48

      110

      125

      220

      230

      Other

      250

      LC1F500 ..

      -

      ED

      FD

      GD

      MD

      -

      Complete Offer

      (*) You can select the contactor proposed or variants. Please consider examples hereafter or follow the link to the complete offer.

      Motor power

      kW

      Coil voltage

      VAC 40...400 Hz

      24

      48

      110

      115

      120

      220

      230

      240

      400

      Other

      250

      LC1F500 ..

      -

      E7

      F7

      FE7

      G7

      M7

      P7

      U7

      V7

      Complete Offer

      (**) You can select the breaker proposed or variants. Please consider examples hereafter or follow the link to the complete offer.

      Motor power

      kW

      ICU (kA)

      F

      Breaker with capacity level

      F

      ICU (kA)

      H

      Breaker with capacity level

      H

      ICU (kA)

      N

      Breaker with capacity level

      N

      Other

      250

      36

      LV432948

      70

      LV432950

      50

      LV432949

      Complete Offer