soft starter for asynchronous motor - ATS01 - 3 A - 110..480V - 0.55..1.1 KW

Show more characteristics >
  • Product availability
    Stock - Normally stocked in distribution facility
  • Price
    100.00 USD
Add to My Products Remove from My Products

  • Main
    range of product
    Altistart 01
    product or component type
    Soft starter
    product destination
    Asynchronous motors
    product specific application
    Simple machine
    device short name
    ATS01
    Phase
    1 phase
    [Us] rated supply voltage
    110...480 V - 10...10 %
    motor power kW
    0.37 kW 3 phases 230 V
    0.55 kW 3 phases 230 V
    1.1 kW 3 phases 400 V
    0.37 kW 1 phase 230 V
    motor power hp
    0.5 hp 3 phases 230 V
    0.5 hp 3 phases 460 V
    1.5 hp 3 phases 460 V
    IcL starter rating
    3 A
    utilisation category
    AC-53B EN/IEC 60947-4-2
    current consumption
    15 A at nominal load
    type of start
    Start with voltage ramp
    power dissipation in W
    19 W in transient state
    4 W at full load and at end of starting
    Complementary
    assembly style
    With heat sink
    function available
    Integrated bypass
    supply voltage limits
    99...528 V
    supply frequency
    50...60 Hz - 5...5 %
    network frequency
    47.5...63 Hz
    output voltage
    <= power supply voltage
    [Uc] control circuit voltage
    110 V AC +/- 10 % 30 mA
    24 V AC/DC +/- 10 % 25 mA
    240 V AC +/- 10 % 65 mA
    starting time
    1 s 100
    5 s 20
    Adjustable from 1 to 5 s
    starting torque
    30...80 % of starting torque of motor connected directly on the line supply
    discrete output current
    2 A DC-13
    3 A AC-15
    tightening torque
    7.08 lbf.in (0.8 N.m)
    electrical connection
    Cage type connector rigid 1 2.5 mm² AWG 14 control circuit
    Cage type connector rigid 1 2.5 mm² AWG 14 power circuit
    Cage type connector rigid 2 1 mm² AWG 17 control circuit
    Cage type connector rigid 2 1 mm² AWG 17 power circuit
    Cage type connector flexible with cable end 1 2.5 mm² AWG 14 control circuit
    Cage type connector flexible with cable end 1 2.5 mm² AWG 14 power circuit
    Cage type connector flexible without cable end 1 2.5 mm² AWG 14 control circuit
    Cage type connector flexible without cable end 1 2.5 mm² AWG 14 power circuit
    Cage type connector flexible with cable end 2 0.75 mm² AWG 18 control circuit
    Cage type connector flexible with cable end 2 0.75 mm² AWG 18 power circuit
    Cage type connector flexible without cable end 2 1 mm² AWG 17 control circuit
    Cage type connector flexible without cable end 2 1 mm² AWG 17 power circuit
    marking
    CE
    operating position
    Vertical +/- 10 degree
    height
    3.94 in (100 mm)
    width
    0.91 in (23 mm)
    depth
    3.94 in (100 mm)
    product weight
    0.35 lb(US) (0.16 kg)
    compatibility code
    ATS01N1
    Motor power range AC-3
    0...0.5 kW at 200...240 V 1 phase
    0...0.5 kW at 200...240 V 3 phases
    0.55...1 kW at 200...240 V 3 phases
    1.1...2 kW at 380...440 V 3 phases
    motor starter type
    Soft starter
    Environment
    electromagnetic compatibility
    Damped oscillating waves level 3 IEC 61000-4-12
    Electrostatic discharge level 3 IEC 61000-4-2
    Immunity to electrical transients level 4 IEC 61000-4-4
    Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3
    Voltage/current impulse level 3 IEC 61000-4-5
    Conducted and radiated emissions level B CISPR 11
    Conducted and radiated emissions level B IEC 60947-4-2
    EMC immunity EN 50082-2
    Harmonics IEC 1000-3-2
    Harmonics IEC 1000-3-4
    Immunity to conducted interference caused by radio-electrical fields level 3 IEC 61000-4-6
    Micro-cuts and voltage fluctuation IEC 61000-4-11
    EMC immunity EN 50082-1
    standards
    EN/IEC 60947-4-2
    product certifications
    B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
    CCC
    CSA
    C-Tick
    GOST
    UL
    IP degree of protection
    IP20
    pollution degree
    2 EN/IEC 60947-4-2
    vibration resistance
    1.5 mm peak to peak 3...13 Hz EN/IEC 60068-2-6
    1 gn 13...150 Hz EN/IEC 60068-2-6
    shock resistance
    15 gn 11 ms EN/IEC 60068-2-27
    relative humidity
    5...95 % without condensation or dripping water EN/IEC 60068-2-3
    ambient air temperature for operation
    14...104 °F (-10...40 °C) without derating
    104...122 °F (40...50 °C) with current derating of 2 % per °C
    ambient air temperature for storage
    -13...158 °F (-25...70 °C) EN/IEC 60947-4-2
    operating altitude
    <= 3280.84 ft (1000 m) without derating
    > 3280.84 ft (1000 m) with current derating of 2.2 % per additional 100 m
    Ordering and shipping details
    Category
    22392 - ATSU01/ATS01 LOW HP SOFT STARTERS
    Discount Schedule
    I11
    GTIN
    00785901534181
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    0.39000000000000001
    Returnability
    Y
    Country of origin
    DE
    Offer Sustainability
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm.
    - - - - - - - Substance 2
    Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    Catalog
    Date
    Size
    Add to My Documents
    Catalog: Soft starters Altistart 01 (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    ATS01 C-TICK certificate of conformity (Version 1.0)
    ATS01 CSA CERTIFICATE (Version 1.0)
    Date 6/19/18
    Size 65.4 KB
    ATS01 EU DECLARATION (Version 1.0)
    Date 4/27/18
    Size 360.8 KB
    E184727 UL GENERIC CERTIFICATES (Version 1.0)
    Date 5/31/18
    Size 25.6 KB
    Instruction Sheet
    Date
    Size
    Add to My Documents
    Instruction Sheet - ATS01N1...FT (Version 07)
    Date 10/30/18
    Size 195.5 KB
    End of Life Information
    Date
    Size
    Add to My Documents
    ALTISTART 01, 0.75 – 15 kW, Product End-of-Life Instructions (Version 1.0)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions
    Mounting on Symetrical (35 mm) Rail or Asymetrical Rail with Adaptor RHZ 66



  • Connections and Schema

    Example of 3-phase Power Supply Connection


    (1)
    A line contactor must be used in the sequence.
    A1 :
    Soft starter
    Q1 :
    Motor circuit-breaker
    KM1 :
    Contactors
    F1, F2 :
    Control protection fuses
    S1, S2 :
    Pushbuttons


  • Technical Description

    Function Diagram


    Us :
    Power supply voltage
    Uc :
    Control supply voltage
    LED 1 :
    Green LED
    LED 2 :
    Yellow LED
    Um :