Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

Schneider Eletric ABE7P16T330 Picture
Discontinued

Range: Advantys Telefast ABE 7

Interfaces for PLCs

ABE7P16T330

Schneider Eletric ABE7P16T330 Picture
Discontinued
Range: Advantys Telefast ABE 7

Interfaces for PLCs

ABE7P16T330

sub-base for plug-in relay ABE7 - 16 channels - relay 12.5 mm

ABE7P16T330  has not been replaced. Please contact your customer care center for more information.
  • Price
    590.00 USD
Add to My Products Remove from My Products

  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions


    (1)
    ABE7BV10 / BV20, ABE7BV10E / BV20E


  • Mounting and Clearance

    Mounting



  • Connections and Schema

    HE10 16 Channels



    Wiring Diagram


    (1)
    Inductive load
    (2)
    Fuse only for ABE7P16T334
    (3)
    ABR7S33 (1 "OF" "DPDT") Ith = 10 A (supplied)
    (4)
    ABS7SC3E (5...48 VDC) Imax. = 1.5 A (not supplied)
    (5)
    ABS7SA3M (24...240 VAC) Imax. = 1.5 A (not supplied)
    (6)
    ABS7SC3BA (24 VDC) Imax. = 2 A (not supplied)
    (7)
    ABE7ACC21 (24 VDC) Imax. = 0.5 A (not supplied)


  • Performance Curves

    Curves for Determining Cable Type and Length According to the Current
    16-channel Sub-base


    L
    Cable length
    IT
    Total current per sub base (A)
    IA
    Average current per channel (mA)
    (1)
    TSXCDP••2 and ABFH20H••0 cables with c.s.a. 0.08 mm2 (AWG 28).
    (2)
    TSXCDP••3 cables with c.s.a. 0.34 mm2 (AWG 22).
    (3)
    Cables with c.s.a. 0.13 mm2 (AWG 26).

    The curves are given for a voltage drop of 1 V in the cable. For n volts tolerance, multiply the length determined from the graph by n.


    Temperature Derating Curves


    (1)
    100 % of channels used
    (2)
    50 % of channels used


    Electrical Durability (in Millions of Operating Cycles) Conforming to IEC 60947-5-1
    DC Loads

    DC12 curves


    DC12
    control of resistive loads and of solid state loads isolated by optocoupler, l/R ≤ 1 ms.

    DC13 curves


    DC13
    switching electromagnets, L/R ≤ 2 x (Ue x Ie) in ms, Ue: rated operational voltage, Ie: rated operational current (with a protective diode on the load, DC12 curves must be used with a coefficient of 0.9 applied to the number in millions of operating cycles)

    AC Loads

    AC12 curves


    AC12
    control of resistive loads and of solid state loads isolated by optocoupler, cos ϕ ≥ 0.9.

    AC14 curves


    AC14
    control of small electromagnetic loads ≤ 72 VA, make: cos ϕ = 0.3, break: cos ϕ = 0.3.

    AC15 curves


    AC15