USA

Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

Schneider Eletric ABE7B20MRM20 Picture

View all Advantys Telefast ABE 7

Advantys Telefast ABE 7 - ABE7B20MRM20

Interfaces for Twido PLC

Schneider Eletric ABE7B20MRM20 Picture
View all Advantys Telefast ABE 7
Advantys Telefast ABE 7 - ABE7B20MRM20
Interfaces for Twido PLC

connection sub-base ABE7 - for Twido modular base - 12 inputs 8 outputs

Show more characteristics >
  • Product availability
    Stock - Normally stocked in distribution facility
  • Price
    267.00 USD
Add to My Products Remove from My Products

  • Main
    range of product
    Advantys Telefast ABE7
    product or component type
    Discrete I/O sub-base
    [Us] rated supply voltage
    24 V DC (controller side)
    24 V DC (sensor/controller side)
    number of channels
    20
    number of terminal per channel
    2
    connections - terminals
    Screw type terminals, clamping capacity: 1 x 0.09...1 x 1.5 mm² AWG 28...AWG 16 flexible with cable end
    Screw type terminals, clamping capacity: 1 x 0.14...1 x 2.5 mm² AWG 26...AWG 12 solid
    Screw type terminals, clamping capacity: 1 x 0.14...1 x 2.5 mm² AWG 26...AWG 14 flexible without cable end
    Screw type terminals, clamping capacity: 2 x 0.09...2 x 0.75 mm² AWG 28...AWG 20 flexible with cable end
    Screw type terminals, clamping capacity: 2 x 0.2...2 x 2.5 mm² AWG 28...AWG 16 solid
    connector destination
    Twido programmable controller
    Complementary
    supply voltage limits
    19...30 V DC conforming to IEC 61131-2 (controller side)
    19...30 V DC conforming to IEC 61131-2 (sensor/controller side)
    discrete input number
    12
    discrete input logic
    Sink
    discrete output number
    2 solid state output(s), 2000 mAat source
    6 relay output(s), 3000 mA
    discrete output voltage
    110...250 V AC relay output(s)
    24 V DC solid state output(s)
    5...30 V DC relay output(s)
    discrete output function
    1 NO
    product compatibility
    TWDLMDA40DTK
    TWDLMDA20DTK
    status LED
    1 LED power ON
    polarity distribution
    1 common/12 channels input
    1 common/2 channels solid state output
    1 common/6 channels relay output
    short-circuit protection
    2 A internal fuse, 5 x 20 mm, fast blow (controller side)
    connector type
    HE-10
    pin number
    26
    fixing mode
    By clips on 35 mm symmetrical DIN rail conforming to IEC 60715
    By screws
    supply current
    <= 2 A
    current per channel
    0.0045 A solid state output(s)
    0.009 A relay output(s)
    switched current
    15 mAfor input
    2000 mAfor solid state output
    3000 mAfor relay output
    current per output common
    10 A relay output
    4 A solid state output
    voltage drop on power supply fuse
    0.3 V
    current state 0 guaranteed
    0.4 mA solid state output(s) (sensor/controller side)
    voltage state 0 guaranteed
    10 V solid state output(s) (sensor/controller side)
    2 V relay output(s) (sensor/controller side)
    current state 1 guaranteed
    5.5 mA solid state output(s) (sensor/controller side)
    voltage state 1 guaranteed
    16 V solid state output(s) (sensor/controller side)
    16.8 V relay output(s) (sensor/controller side)
    electrical durability
    500000 cycles, maximum switching current: 2000 mA AC-12 relay output(s) (preactuator side)
    500000 cycles, maximum switching current: 2000 mA DC-12 solid state output(s) (preactuator side)
    500000 cycles, maximum switching current: 2000 mA DC-13 solid state output(s) (preactuator side)
    500000 cycles, maximum switching current: 3000 mA DC-12 relay output(s) (preactuator side)
    500000 cycles, maximum switching current: 400 mA AC-15 relay output(s) (preactuator side)
    500000 cycles, maximum switching current: 500 mA DC-13 relay output(s) (preactuator side)
    minimum switching current
    1 mA solid state output(s)
    100 mA relay output(s)
    response time
    <= 0.01 ms from state 0 to 1 solid state output(s)
    <= 0.4 ms from state 1 to 0 solid state output(s)
    <= 2.5 ms from state 1 to 0 relay output(s)
    <= 5 ms from state 0 to 1 relay output(s)
    [Uimp] rated impulse withstand voltage
    6 kV relay output(s)
    2.5 kV solid state output(s)
    switching frequency
    20 Hz relay
    300 Hz solid state
    mechanical durability
    20000000 cyclesat 68 °F (20 °C)
    [Ui] rated insulation voltage
    2000 V between terminals/mounting rails
    300 V between coil circuit/contact circuits conforming to IEC 60947-1
    overvoltage category
    II conforming to IEC 60664-1
    tightening torque
    5.31 lbf.in (0.6 N.m) (with flat Ø 3.5 mm)
    product weight
    0.95 lb(US) (0.43 kg)
    Environment
    standards
    IEC 61131-2 Type 1
    product certifications
    CSA
    UL
    IP degree of protection
    IP2x conforming to IEC 60529
    resistance to incandescent wire
    1382 °F (750 °C) conforming to IEC 60695-2-11
    shock resistance
    15 gn 11 ms conforming to IEC 60068-2-27
    vibration resistance
    2 gn (f = 10...150 Hz) conforming to IEC 60068-2-6
    resistance to electrostatic discharge
    4 kV (contact) conforming to IEC 61000-4-2 level 3
    8 kV (air) conforming to IEC 61000-4-2 level 3
    resistance to radiated fields
    9.14 V/yd (10 V/m) (80000000...2000000000 Hz) conforming to IEC 61000-4-3 level 3
    resistance to fast transients
    2 kV conforming to IEC 61000-4-4 level 3
    ambient air temperature for operation
    23...140 °F (-5...60 °C) conforming to IEC 61131-2
    ambient air temperature for storage
    -40...176 °F (-40...80 °C) conforming to IEC 61131-2
    pollution degree
    2 conforming to IEC 60664-1
    Ordering and shipping details
    Category
    22375 - INTERFACE MODULE(ABA,R,S)
    Discount Schedule
    CP2
    GTIN
    00785901572251
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    0.79000000000000004
    Returnability
    Y
    Country of origin
    LV
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • French
    Catalog
    Date
    Size
    Add to My Documents
    Date 7/14/18
    Size 8.8 MB
    CAD
    Date
    Size
    Add to My Documents
    ABE7B sub-bases for TWIDO controllers
    REACh Declaration
    Date
    Size
    Add to My Documents
    RoHs Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions


    (1)
    ABE7BV10 / BV20 / BV20TB


  • Mounting and Clearance

    Mounting



  • Connections and Schema

    HE10 20 Channels



    Wiring Diagram


    (1)
    Inductive load
    (2)
    Input sink


  • Performance Curves

    Curves for Determining Cable Type and Length According to the Current


    L
    Cable length
    IT
    Total current per sub base (A)
    IA
    Average current per channel (mA)
    (1)
    Cables ABFT2••••• c.s.a. 0.08 mm2 (AWG 28)

    The curves are given for a voltage drop of 1 V in the cable. For n volts tolerance, multiply the length determined from the graph by n.


    Temperature Derating Curves
    Electromechanical Relay Outputs


    (1)
    100 % of channels used
    (2)
    50 % of channels used


    Temperature Derating Curves
    Solid State Outputs



    Electrical Durability (in Millions of Operating Cycles) Conforming to IEC 60947-5-1
    DC Loads

    DC12 curves


    DC12
    control of resistive loads and of solid state loads isolated by optocoupler, l/R ≤ 1 ms.

    DC13 curves


    DC13
    switching electromagnets, L/R ≤ 2 x (Ue x Ie) in ms, Ue: rated operational voltage, Ie: rated operational current (with a protective diode on the load, DC12 curves must be used with a coefficient of 0.9 applied to the number in millions of operating cycles)

    AC Loads

    AC12 curves


    AC12
    control of resistive loads and of solid state loads isolated by optocoupler, cos ϕ ≥ 0.9.

    AC14 curves


    AC14
    control of small electromagnetic loads ≤ 72 VA, make: cos ϕ = 0.3, break: cos ϕ = 0.3.

    AC15 curves


    AC15
    control of electromagnetic loads > 72 VA, make: cos ϕ = 0.7, break: cos ϕ = 0.4.