Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

Schneider Eletric ABA6PT311 Picture
Discontinued

Range: Zelio Analog

Converters

ABA6PT311

Schneider Eletric ABA6PT311 Picture
Discontinued
Range: Zelio Analog

Converters

ABA6PT311

temperature transmitter - 0..100 °C/32..212 °F - for Universal Pt100 probes

Show more characteristics >
  • Price
    678.00 USD
Add to My Products Remove from My Products

ABA6PT311 is replaced by:
Product
Qty
RMPT30BD
Qty
1
Add to My Products Remove from My Products
  • Reason for Substitution: End of life
  • Substitution date: 01 January 2017
  • Main
    range of product
    Zelio Analog
    product or component type
    Converter for Universal Pt100 probes
    analogue input type
    Temperature probe 0...100 °C/32..212 °F Pt 100 2, 3 or 4 wires
    analogue output type
    Current 0...20 mA <= 500 Ohm
    Current 4...20 mA <= 500 Ohm
    Voltage 0...10 V >= 100 kOhm
    Complementary
    protection type
    Overvoltage protection on output (+/- 30 V)
    Reverse polarity protection on output
    Reverse polarity protection on power supply
    Short-circuit protection on output
    abnormal analogue output voltage
    +/- 13 V when no input wired or wire broken
    abnormal analogue output current
    0 A when no input wired or wire broken
    [Us] rated supply voltage
    24 V DC non isolated +/- 20 %
    current consumption
    <= 40 mA voltage output
    <= 60 mA current output
    local signalling
    LED green (power ON)
    measurement error
    +/- 0.5 % of full scale (3 or 4 wires) at 20 °C
    +/- 1 % of full scale (2 wires) at 20 °C
    +/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m)
    repeat accuracy
    +/- 0.2 % full scale at 20 °C
    +/- 0.6 % full scale at 60 °C
    temperature coefficient
    150 ppm/°C
    maximum wiring resistance
    0.2 Ohm connection in 2 wires
    clamping connection capacity
    1 x 2.5 mm²
    2 x 1.5 mm²
    tightening torque
    5.31...9.73 lbf.in (0.6...1.1 N.m)
    marking
    CE
    surge withstand
    0.5 kV 1.2/50 µs conforming to IEC 61000-4-5
    [Ui] rated insulation voltage
    2000 V
    fixing mode
    Clip-on, 35 mm symmetrical DIN rail
    Fixed, mounting plate
    safety reliability data
    MTTFd = 32.9 years
    B10d = 30437
    product weight
    0.26 lb(US) (0.12 kg)
    Environment
    electromagnetic compatibility
    Electrostatic discharge (test level: 6 kV, level 3 - contact discharge) conforming to IEC 61000-4-2
    Electrostatic discharge (test level: 8 kV, level 3 - air discharge) conforming to IEC 61000-4-2
    standards
    DIN 43760
    EN/IEC 60584-1
    EN/IEC 60751
    EN/IEC 60947-1
    product certifications
    CSA
    GL
    UL
    IP degree of protection
    IP20 terminal block
    IP50 housing
    fire resistance
    1562 °F (850 °C) conforming to IEC 60695-2-1
    1562 °F (850 °C) conforming to UL
    shock resistance
    50 gn 11 ms conforming to IEC 60068-2-27
    vibration resistance
    5 gn (f = 10...100 Hz) conforming to IEC 60068-2-6
    resistance to fast transients
    1 kV on input-output conforming to IEC 61000-4-4
    2 kV on power supply conforming to IEC 61000-4-4
    disturbance radiated/conducted
    CISPR 11
    CISPR 22 group 1 - class B
    ambient air temperature for storage
    -40...185 °F (-40...85 °C)
    ambient air temperature for operation
    32...122 °F (0...50 °C) (mounting side by side)
    32...140 °F (0...60 °C) (2 cm spacing)
    pollution degree
    2 conforming to IEC 60664-1
    Ordering and shipping details
    Category
    22375 - INTERFACE MODULE(ABA,R,S)
    Discount Schedule
    CP2
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    0.16
    Returnability
    N
    Country of origin
    FR
    Contractual warranty
    Warranty period
    18 months
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.