Schneider Electric USA Website

Welcome to our website.

To view product availability in a specific country, select from the country list below. For Investor Relations, please visit our global site.

Choose another country or region

    Share

    Copy Cancel
    Schneider Eletric 140SDO95300S Picture

    Range: Modicon Quantum PAC

    Safety applications

    140SDO95300S

    Schneider Eletric 140SDO95300S Picture
    Range: Modicon Quantum PAC

    Safety applications

    140SDO95300S

    safety dc discrete output module - 16 outputs - 19.2..30 V DC

    Show more characteristics >
    • Product availability
      Non-Stock - Not normally stocked in distribution facility
    • Price
      3275.00 USD
    Add to My Favorites Remove from My Favorites

    • Main
      range of product
      Modicon Quantum automation platform
      product or component type
      Safety dc discrete output module
      Complementary
      discrete output number
      16
      group of channels
      1
      discrete output logic
      Positive logic (source)
      addressing requirement
      7 input words
      4 output words
      discrete output voltage
      19.2...30 V DC
      absolute maximum output
      34 V
      voltage drop
      <= 0.3 V 0.5 A
      sensor power supply
      19.2...30 V
      maximum load current
      <= 0.65 A each point
      <= 10.04 A each group
      surge current
      2 A for 10 ms
      response time
      <= 20 ms at state 0 to state 1
      <= 20 ms at state 1 to state 0
      leakage current
      0.5 mA 30 V
      protection type
      With
      load inductance
      Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))
      0.5 8 Hz
      fault indication
      System fault
      Power supply fault
      Channel fault
      Overload
      associated fuse rating
      10 A
      isolation between channels and bus
      1500 Vrms for 1 minute
      isolation between group and bus
      1500 Vrms for 1 minute
      power dissipation
      1.9 W + 0.65 I²
      marking
      CE
      local signalling
      1 LED green bus communication is present (Active)
      1 LED red external fault detected (F)
      16 LEDs green output status
      16 LEDs red system failure, diagnostic of internal channel fault
      bus current requirement
      350 mA
      Environment
      product certifications
      UL
      CSA HazLoc
      TÜV Rheinland (SIL2)
      CSA
      C-Tick
      Ordering and shipping details
      Category
      18151 - SIL 2 QUANTUM
      Discount Schedule
      PC21
      GTIN
      00785901865384
      Nbr. of units in pkg.
      1
      Package weight(Lbs)
      2.2000000000000002
      Returnability
      N
      Country of origin
      FR
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  0749  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Available
      Product end of life instructions
      Available
      Contractual warranty
      Warranty period
      18 months
    • Documents and Downloads

      Language
      • English
      Catalog
      Date
      Size
      Add to My Documents
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
    • Dimensions Drawings

      Racks for Modules Mounting
      Dimensions of Modules and Racks


      (1)
      2 slots
      (2)
      3 slots
      (3)
      4 slots
      (4)
      6 slots
      (5)
      10 slots
      (6)
      16 slots


    • Connections and Schema

      24 Vdc/0.5 A Source Overload Detection 16-Channel Digital Output Module
      Wiring Diagram


      fuse:
      10 A max (determined by the module load current), fast blow
      pre-act:
      pre-actuator

      NOTE: There is only one group of 16 outputs. All common 24 V are internally connected and all common 0V are also internally connected. The two pins of a same input (e. g: pin 1 and 2 for input 1) are internally connected too so that you can use either the right pin or the left one.