Range: Modicon Quantum PAC

Safety applications

140SDI95300S

Schneider Eletric 140SDI95300S Picture
Range: Modicon Quantum PAC

Safety applications

140SDI95300S

safety dc discrete input module - 16 inputs - 24 V DC

Show more characteristics >
  • Product availability
    Non-Stock - Not normally stocked in distribution facility
  • Price
    2334.00 USD
Add to My Products Remove from My Products

  • Main
    range of product
    Modicon Quantum automation platform
    product or component type
    Safety dc discrete input module
    Complementary
    discrete input number
    16
    group of channels
    1
    logic input
    Positive (sink)
    discrete input voltage
    24 V DC
    voltage state 1 guaranteed
    11...30 V DC
    voltage state 0 guaranteed
    -3...5 V DC
    current state 1 guaranteed
    >= 3 mA
    current state 0 guaranteed
    <= 1.5 mA
    sensor power supply
    19.2...30 V
    addressing requirement
    7 input words
    input impedance
    3675 Ohm
    absolute maximum input
    30 V
    response time
    <= 25 ms from state 0 to state 1
    <= 25 ms from state 1 to state 0
    protection type
    By internal rectifier
    associated fuse rating
    1 A fast blow
    power dissipation
    2.75 W + (0.25 x number of points on)
    isolation between group and bus
    1500 Vrms for 1 minute
    checks
    Broken wire detection
    Diagnostic of internal channel fault
    System failure
    local signalling
    1 LED green bus communication is present (Active)
    1 LED red external fault detected (F)
    16 LEDs green input status
    16 LEDs red system failure, diagnostic of internal channel fault
    marking
    CE
    bus current requirement
    550 mA
    Environment
    product certifications
    CSA
    CSA HazLoc
    TÜV Rheinland (SIL2)
    UL
    Ordering and shipping details
    Category
    18151 - SIL 2 QUANTUM
    Discount Schedule
    PC21
    GTIN
    00785901865377
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    2.2000000000000002
    Returnability
    N
    Country of origin
    FR
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Product end of life instructions
    Available
    California proposition 65
    WARNING: This product can expose you to chemicals including:
    - - - - - - - Substance 1
    Lead and lead compounds which is known to the State of California to cause cancer and birth defects or other reproductive harm.
    - - - - - - - More information
    For more information go to www.p65warnings.ca.gov
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • French
    Catalog
    Date
    Size
    Add to My Documents
    User guide
    Date
    Size
    Add to My Documents
    Certificate
    Date
    Size
    Add to My Documents
    UL_E486184_NRAQ-NRAQ7_ALL_JUN2018
    ATEX-IECEx
    Date 6/19/18
    Size 2.2 MB
    Date 6/19/18
    Size 100.6 KB
    Date 6/19/18
    Size 1.5 MB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Racks for Modules Mounting
    Dimensions of Modules and Racks


    (1)
    2 slots
    (2)
    3 slots
    (3)
    4 slots
    (4)
    6 slots
    (5)
    10 slots
    (6)
    16 slots


  • Connections and Schema

    24 Vdc 16-Channel Digital Input Module
    Wiring Diagram


    fuse:
    1 A fast blow
    pull-up resistor (in sensor example):
    15 kOhm

    NOTE: There is only one group of 16 inputs. All common 24 V are internally connected and all common 0 V are also internally connected. The two pins of a same input (e. g: pin 1 and 2 for input 1) are internally connected too so that you can use either the right pin or the left one.