What is the rating of the number of switching operations of Square D, 100A, Heavy Duty, F-Series Safety Switches? These ratings are also sometimes referred to as Endurance operations and Horsepower-overload operations.

Issue:
100A, Heavy Duty, F-Series Safety Switches number of switching operations.

Product Line:
Safety Switch

Environment:
Heavy Duty Safety Switch

Resolution:
For Safety Switches, the standard for design and testing of the number of switching operations is governed by UL98 and NEMA KS-1.There are two separate tests: (1) Endurance Test, and (2) Horsepower-overload test. The below table shows the minimum number of operations required (OFF to ON to OFF) by UL and NEMA. For the endurance test, however, Square D 100A F-Series Safety Switches exceed the UL and NEMA requirements by more than 3 times the total (see below table):  
 
                               100A, Square D Heavy Duty Safety Switches (F-series)
  Endurance Test - Number of Operations HP Test - Number of Operations
Test Stds Rated Load* No Load Total (Load + No Load) at rated HP**
UL 6000 4000 10000 50
NEMA 7000 7000 14000 50
Square D 7000 43000 50000 50
* Endurance test performed at switch rated load current
** Horsepower test - make/break motor inrush/locked rotor current at rated HP

Number of switching operations for other Heavy Duty Safety Switches:
For 30-60A series F Heavy Duty safety switches, see FA99746
For 200A series F Heavy Duty safety switches, see FA99791
For 400A series E Heavy Duty safety switches, see FA99792
For 600A series E Heavy Duty safety switches, see FA99819
For 800A series E Heavy Duty safety switches, see FA99821
For 1200A series E Heavy Duty safety switches, see FA99822