What is the conductor(or Main Wire) temperature rating for the lugs of ALL the EZM Main Devices (Main Breaker, Main Switch and Main Lug)?

Issue:
Application

Product Line:
EZM

Cause:
Application

Resolution:
The UL standards only test using 75 degree C conductor(or wire) so even though it might be marked on the lug itself stating '90 degree C', the devices are all UL tested and listed for use with 75 degree C Conductors.
NOTE: 90 degree C conductors may be used if installed in accordance with the NEC (National Electrical Code), following the 75 degree C table.