Can a transformer for a 1 phase load work off a 3 phase power source?
ISSUE
Three Phase power sources are often used to feed single phase Transformers
PRODUCT LINE
LV Transformers
ENVIRONMENT
Applies to all Single Phase Transformers from SquareD/Schneider Electric
CAUSE
Three Phase power is a common Distribution System for Industrial applications
RESOLUTION
Yes. A single phase transformer can be fed from either a line-to-line or a line-to neutral source. Simply match the primary voltage rating of the transformer to the available source voltage.