What are the acceptable wire sizes and torque values for the GV1G09 and GV2G05?

Issue:
What are the acceptable wire sizes and torque values for the GV1G09 and GV2G05?

Product Line: 
Digest 177 Section 16 : Nema and Definite Purpose and Starters

Environment:
North American Products

Resolution:
 Solid cable:
(1) #14 to #2 AWG conductor or
(2) #14 to #6 AWG conductors

Flexible cable without cabel end:
(1) #14 to #2 AWG conductor or
(2) #12 to #6 AWG conductors

Flexible cable with cabel end:
(1) #14 to #4 AWG conductor or
(2) #14 to #10 AWG conductors

Tightening Torque:
Connector = 20 lb-in
Screw Clamp = 15 lb-in

 