Can an 8536 non-reversing starter be converted to a reversing starter?

Issue:
Wants to convert an 8536 non-reversing starter to a reversing starter.

Product Line:
8536 Starters

Environment:
NEMA Contactors and Starters

Resolution:
Yes. The following additional components will be needed: an additional 8502 contactor of the same NEMA size, a mechanical interlock, and two auxiliary interlocks.
 