Will the I-line panel accept a QO breaker?

Issue:
Can QO breakers be mounted in an I-line panel?

Product Line:
Panelboards

Environment:
I-Line Panelboards

Resolution:
Yes, by using a QO Distribution panel rated for 240V and below . They will all accept 30A max breakers and have 6 single spaces for QO plug on breakers. They take 4.5`` of mounting space. The following items are available.
HQO306
HQO206AB
HQO206AC
HQO206BC
See 48040-902-02