How do I get my two wire control circuit to work on a mechanically held lighting contactor?

Issue:
How do I get my two wire control circuit to work on a mechanically held lighting contactor?

Product Line:
NEMA lighting Contactors

Environment:
Products sold and used in the United States

Cause:
Two wire control needed for a mechanically held lighting contactor

Resolution:
You may order the lighting contactor with form R6 to obtain a factory installed 2-wire control relay. If a field installable kit is preferred, order a CA2SK11 relay with proper voltage code and a 9999RLX mounting bracket for the 8903 type LX. For the 8903 Type SM, SP, SQ, SV, or SX order an 8501XO11 relay with proper voltage code.

 