Can GC200 ground fault unit be used on both DELTA and WYE systems?

Issue:
Can GC200 be used on delta and wye systems?

Product Line:
Circuit Breakers

Resolution:
The system must be solidly grounded. Not on an ungrounded DELTA. Generally, only WYE systems are solidly grounded.