Is the UFP222R, AC Disconnect suitable for use as service equipment?

Issue:
Product Design Features 

Product Line:
AC Disconnect

Environment:
Service Entrance Rated

Cause:
Application

Resolution:
NOTE - the UFP222R IS OBSOLETE, NO LONGER AVAILABLE WITH NO DIRECT REPLACEMENT. LOOK AT THE ENCLOSED MOLDED CASE SWITCHES

The device is suitable for use as service equipment on a 120/240Vac, 1ph-3w service if used only on a 1ph-2w load; and only when the equipment grounding terminal supplied is replaced with ground bar kit, catalog number PK3GTA1.


 