What X/R ratio are circuit breakers short-circuit tested at?

Issue:
What X/R ratio are breakers tested at?

Product Line:
Circuit Breakers

Resolution:
Circuit breakers with an AIR of 20 kA or more are tested with a power factor 15% to 20%; X/R ratio = 4.9 to 6.6.