What is the standard wire range(or terminal data) of the lugs used in the EZM11600TB and EZM31600TB?

Issue:
product design features 

Product Line:
EZM Metering

Environment:
Main lug wire range 

Cause:
Installation 

Resolution:
The EZM11600TB and EZM31600TB Main Terminal boxes will accept as standard (6) 1/0-600 OR (12) 1/0-300 kcmil Al/Cu Wires per phase and neutral. The Ground Lug will accept (1) #6 - 300kcmil Al/Cu wire. For the EZM11600TB SEE CAD DRAWING #3373 and for the EZM31600TB SEE CAD DRAWING #3374.

 