What Class of fuse does ALL the 600amp Heavy Duty Safety Switches Accept( Like the H226, H226NAWK, H366, H366DS, H366NDS, H366AWK)?

Issue:
Product design features

Product line:
Heavy Duty Safety Switches

Environment:
Fuse Class

Cause:
Application

Resolution:

These switches accept Class H or K fuses as standard. Options include Class R fuses (field install Class R Fuse Kit HRK4060) and Class J fuses requires the field installed Class J Adaptor Kit H600J. With Class H or K fuses installed, the switches are UL listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R or J fuses and the appropriate fuse kit installed, the switches are UL listed for use on systems with up to 200,000 RMS Symmetrical Amperes available fault current.

NOTE: DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability and will void the warranty.