Technical FAQs

Ask a Question

Does the shorting contactor need to be oversized if it is to be used for full voltage bypass?

Issue:
Does the shorting contactor need to be oversized if it is to be used for full voltage bypass?

Product Line:
Altistart Soft Starters

Environment:
All

Cause:
NA

Resolution:

Yes. Shorting contactors are only rated for the AC1 rating. This means it is only rated to handle the continuous amps for the motor. It will be too small to handle the starting current. It is necessary to select full voltage bypass contactors based on the AC3 rating to handle the motor starting current.
It is also recommended to use external overload protection because the soft starter will not be able to provide the motor thermal protection when removed from the circuit for full voltage bypass.


CTA-ID : 7482
Was this helpful?
What can we do to improve the information ?