Are the Square D Heavy Duty Safety Switches UL listed as Suitable for Use as Service Equipment?

Issue:
Product design features
 
Product Line:
Heavy Duty Safety Switches
 
Environment:
Service Entrance
 
Cause:
Application
 
Resolution:
Yes, IN GENERAL, most 2 and 3-pole single-throw switches are suitable for use as service entrance equipment when equipped with a field or factory installed Neutral Assembly or Equipment Ground kit, unless a 600Y/347 volt or 480Y/277 volt, 1,000 ampere or greater, solidly grounded Wye system is used, per the National Electrical Code. There are exceptions to the service equipment listing, notibly the 4 and 6 pole switches.
NOTES:
1) For Special Application switches, see each individual catalog number or contact Square D for more details. 
2) For Double Throw Switches(see FA87564) 
For both of the above notes, refer to the current on-line digest for information.
 


 