Is there a 200 amp EDB like catalog # EDB34200?

Issue:
Is an EDB breaker rated over 125 A available?

Product Line:
NF Panelboard Branch Breakers

Resolution:
No. The largest EDB breaker would be 125A like catalog number EDB34125. For a 200 A breaker, a subfeed breaker kit and breaker could be added. This would increase the box size of the panel, however.