What is the Padlock Attachment for the 2 and 3 pole QOU breakers?

Issue:
2 Pole and 3 Pole QOU Breakers Padlock Attachment

Product Lines:
QOU Breakers
 
Environment:
In applications using DIN rail or unit mount breakers
 
Cause:
Need to padlock a QOU breaker
 
Resolution:
The padlock options are in the below table.
 
Padlocking Function Catalog # Instruction Bulletin
For padlocking 2- and 3-pole circuit breakers up to 70 A in “OFF” or “ON” position
Attaches to circuit breaker escutcheon—Fixed
QOU1PL 40272-201-03
For padlocking 2- and 3-pole circuit breaker in “OFF” position only (1- and 2-pole 10–70 A, 3-pole 10–60 A) QOU2PAFLA 48840-210-01
Two-and 3-pole circuit breakers. Attaches to circuit breaker handle—Removable QO1HPL 48840-158-01
For padlocking 2- and 3-pole circuit breakers 80 A and above in "OFF" position only Suffix -7100 N/A