Technical FAQs

Ask a Question

Is a UL 489 listed non-automatic switch available in the Masterpact NW frame?

Issue:
Needs UL 489 listed masterpact non-automatic switch
 
Product Line:
Air Circuit Breaker
 
Environment:
Masterpact NT and NW
 
Cause:
Product selection
 
Resolution:
 
No. An automatic switch is available with UL 489 and IEC 947-3 listings.
 
A non-automatic switch is available with ANSI C37 certification, UL 1066 Listing, and with IEC 947-3 listing.  
Was this helpful?
What can we do to improve the information ?