What is the torque spec for the MAL36600 circuit breaker?

Issue:
What is the torque spec for the lugs on an MAL36600 circuit breaker?

Product Line:
Molded Case circuit breakers

Environment:
Installation

Cause:
Specification

Resolution:
The wire binding torque spec. for the AL900MA is 300 lb.-in. Lug mounting torque is 180 lb-in.


 