Are the FAL/FHL breakers DIN rail mountable?

Issue:
Are the FAL/FHL breakers DIN rail mountable?

Product Line:
FAL/FHL Molded Case Circuit Breakers

Environment:
This would apply to unit mount breakers only it would not apply to I-Line breakers.

Cause:
Want to be able to DIN rail mount the breakers in a panel.

Resolution:
No, FAL/FHL breakers do not have a DIN rail mounting adapter available.

Powerpact H & J frame 3-pole breakers can be DIN rail mounted. Use kit # S29305.  
DIN rail mounting kit (requires 15 mm depth on a 35 mm DIN rail)
Fits 3 pole module breakers only. (Not available in 2 pole)

See instruction bulletin, 48940-239-01.