What is the temperature rating on QO circuit breaker terminations?

Published date: 29 August 2019

Issue:
Temperature for QO breaker

Product Line:
Miniture Circuit Breaker

Environment:
QO Breaker

Resolution:
10-30 amp breakers can use 60 or 75 degree C conductors.
35-150 amp breakers can use 75 degree C conductors.