Browse FAQs

On an ATV212 can the analog input be programmed for 0-10V to control 30-60Hz?

Published date: 18 September 2019

Issue:
The  ATV212 needs the  analog input programmed for 0-10V to control 30-60Hz.

Product Line:
Altivar 212

Environment:
All

Cause:
Wants 0-10V to equal 30-60Hz

Resolution:
Yes, this is accomplished by adjusting the scaling of the applicable analog input so that the drive knows that 0%=30Hz. 

If you're using VIA: Adjust F202 to 30Hz
If you're using VIB: Adjust F211 to 30Hz 

For details on accessing these parameters please see the FAQ on ATV212 Basic Programming.

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.