Video: How to install M2C or M6C programmable contacts into a P-frame or R-frame breaker

Issue:
How do you install the M2C or M6C contacts in a Powerpact P-frame or R-frame circuit breaker?

Product Line:
Powerpact P-frame and R-frame Accessories

Resolution:

First, remove the accessory cover from the breaker. Remove the trip unit by sliding the green 12-pin connector out on top, loosening the screws on top and bottom of the trip unit, and sliding it out. Connect the connectiion piece on the contacts to the specific spot on the breaker, and tighten the two screws on the piece. Reinstall the trip unit back into place. For more information, see the video below:

[video placeholder]