Video: Where is the instantaneous dial on an I-Line J-Frame breaker located?

Issue:
How do you change the instantaneous setting on an I-line installed PowerPact J-Frame circuit breaker?

Product Line:
Molded Case Circuit Breakers

Resolution:
The I-line deadfront covers up the instantaneous dial on a J-frame. Therefore, the deadfront would have to be removed, and then the instantaneous dial is on the bottom of the breaker, and can be adjusted.

The following video demonstrates this procedure: