What is the difference between an AL150HD and AL150HDS?

Issue:
Clarification on AL150HD and AL150HDS

Product Line:
Molded Case Circuit Breaker

Environment:
Powerpact H-Frame Lugs

Resolution:
The main difference is the wire binding screw and terminal wire range as follows:
The AL150HD has terminal wire range of 14-10AWG and would need hex screw 3/16 inch (4.8mm) wrench size with 50 lb-in wire binding torque.
The AL150HDS has terminal wire range of 8-30AWG and would need hex screw 5/32 inch (4.0mm) wrench size with 120 lb-in wire binding torque.

See instruction bulletin 48940-221-02.