What are the coil voltage operating limits on the 8501K relays?

Issue:
Minimum and maximum voltages that can be applies on the AC and DC coils for the 8501 Type K relays

Product Line:
General Purpose Relays

Environment:
Class 8501 Type K relays

Resolution:
Below are the operating limits. Also, attached is the page from the catalog that lists the information.

DC Voltage:
12V - 9.6 to 13.2 VDC
24V - 19.2 to 26.4 VDC
48V - 38.4 to 52.8 VDC
110V - 88 to 121 VDC


AC Voltage:
24V - 19.2 to 26.4 VAC
120V -  96 to 132 VAC
240V - 192 to 264 VAC