Issue:
Can you add a fuse block on a non-fusible 8538SFA21 size 4 combo starter to convert to fusible?

Product Line:
Class 8538 Type SF Series C Combination Starter

Environment:
Products sold and used in the United States

Resolution:
You cannot add a fuse block on the combo starter. You have to swap out the complete switch as the fuse block is integral of the switch.

Complete disconnect switch part number is 3105536650.  