It is possible to configure Lexium 28 for Automatic Enable in which the drive will Enable as soon as power has been applied.

This will be true provide there are no errors preventing the drive from enabling.

Start by assigning the first digital input as the Enable input, and configure the input to be a normally close type contact.
Do this by adjusting parameter P2-10 to 0001.

Next adjust parameter P2-68 for "Enable Power Stage Automatically if SON input is active" .
Do this by setting P2-68 to 0001.

Now power cycle the drive for the settings to be accepted.

The drive will now automatically enable when the power is applied and no errors are present.

 