How to properly wire a 9070T*D92?

Issue: 
Wiring  a 9070T*D92

Product Line:
LV/LV XFMR

Environment:
Installation/maintenance 

Resolution: 
Primary: 
230: Connect to H1 and H4
Jumper H1 with H3
Jumper H2 with H4

460: Connect to H1 and H4
Jumper H2 with H3

Secondary :
24v: Connect to X1 and X2


https://download.schneider-electric.com/files?p_enDocType=Catalog&p_File_Name=9070CT9901R805.pdf&p_Doc_Ref=9070CT9901