Can the ATV630, ATV930 Process Drive be used on a Corner Grounded or "Dead Leg" System?

Issue:
Can the ATV630, ATV930 Process Drive be used on a Corner Grounded or "Dead Leg" System?

Product Line:
Process Drive

Environment:
All 

Cause:
IT ungrounded system

Resolution:
Drive is on a corner grounded IT System so disable the EMC Filter, per the Installation Manual.