Unity Pro Debug screen forcing I/O

Issue:
Force is grayed out in the Unity Pro I/O module Debug screen.

Product line:
Unity Pro, x80

Resolution:
To force x80 I/O from the module debug screen the I/O module needs to be configured with and I/O data type of Topological. If the module is configured with an I/O data type is Device DDT, force is not available.